Siemens SIMATIC PCS 7 Operation And Maintenance page 70

Process control system pcs 7 compendium part d
Hide thumbs Also See for SIMATIC PCS 7:
Table of Contents

Advertisement

Service and maintenance of SIMATIC PDM
6.6 Replacing/removing field devices
PA device (PDM V9.1) procedure
In this example, a Siemens SITRANS LR250 level radar is replaced with a Siemens
SITRANS LR260 level radar.
1. In HW Config, select "Object Properties" from the shortcut menu of the LR250.
2. Back up all project-specific information and settings from the "General" and "Assign
Parameters" tabs. You will need this information for configuring and assigning parameters
for the new device type.
3. Make a backup of the symbol table (E address).
4. Switch to the process device plant view to back up the LR250 parameter set.
SIMATIC PDM opens.
5. Select the device "LR250_Compend" and select "Export..." in the shortcut menu.
The export dialog is opened. Using the export dialog, you can back up the device
parameters and diagnostics and document manager information.
70
Compendium Part D - Operation and Maintenance (V9.0)
Operating Manual, 02/2018, A5E43228948-AA

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents