Wiring; Humidity Selector; Electrical Connections; 115-Vac Wiring - Bryant HRVBBLHU Installation, Start-Up, And Operating Instructions Manual

Heat recovery ventilator
Hide thumbs Also See for HRVBBLHU:
Table of Contents

Advertisement

MODE
DEHUMIDISTAT POSITION
Off
Any
Satisfied
Low
Call for dehumidification
Satisfied
Intermittent
Call for dehumidification
MODE
DEHUMIDISTAT POSITION
Off
Any
Satisfied
Intermittent
Call for dehumidification
Satisfied
Continuous
Call for dehumidification
Satisfied
Recirculation
Call for dehumidification
Any
Any
OUTSIDE TEMPERATURE
50° F
32° F
14° F
-4° F
-22° F
If the level of humidity falls too low in the winter months while operating in the continuous exchange mode, a humidifier may be integrated into the system. Intermittent
exchange mode may also be selected for short periods of time to increase the level of humidity.
V. WIRING
Remove top cover assembly from wall control and pass thermostat
wire through hole located on back of control before attaching to
wall. Connect Y, R, G, and B (yellow, red, green and black)
between wall control and HRV circuit board. Following color code
(See Fig. 11 and 12). Replace top cover assembly.
NOTE: HRV wall control and circuit board operate on 12vdc.
Y
R
GB
Fig. 11—Typical Wall Control
TABLE 2—STANDARD CONTROL
OPERATION
Off
Off
Air exchange with outside
Air exchange with outside
Air exchange with outside
TABLE 3—AUTOMATIC CONTROL
OPERATION
Off
Air exchange with outside
Air exchange with outside
Air exchange with outside
Air exchange with outside
Recirculation
Air exchange with outside
Any
TABLE 4—RECOMMENDED HUMIDITY LEVELS
10° C
0° C
-10° C
-20° C
-30° C
YELLOW
RED
GREEN
BLACK
A98383
—7—
DAMPER POSITION
FAN SPEED
Closed to outside
Open to outside
Open to outside
Closed to outside
Open to outside
DAMPER POSITION FAN SPEED
Closed to outside
Off
Open to outside
Off
Open to outside
High
Open to outside
Low
Open to outside
High
Closed to outside
High
Open to outside
High
Any
DOUBLE-PANE
WINDOWS
55 percent
45 percent
35 percent
30 percent
25 percent
VI. HUMIDITY SELECTOR
The humidity selector is a built-in dehumidistat designed to
properly control the level of humidity in the house during the
winter months. This control helps avoid condensation problems in
upper northern regions where indoor humidity is a problem during
the winter season.
NOTE: This control is not to be confused with a dehumidistat
used during the summer months to control high relative indoor
humidity.
Table 4 recommends humidity levels to avoid condensation.

ELECTRICAL CONNECTIONS

I. 115-VAC WIRING
The HRV operates on 115vac. It comes with a power cord attached
to unit and ready to plug into a fused outlet. Unit must be grounded
for proper operation.
All electrical connections must comply with National and Local
Electrical Codes, or other ordinances that might apply.
WARNING: ELECTRICAL / FIRE HAZARD
Failure to follow this warning could result in property or
unit damage.
Do not use an extension cord as a power source for
operating the HRV.
II. 12-VDC WIRING
The HRV circuit board, wall control, and accessories operate on
12vdc. See Wall Control section, item Wiring and Fig. 11 and 12
for more information.
ON
AIR EXCHANGE
LED
LED
Off
Off
Off
Low
On
Off
High
On
On
Off
On
Off
High
On
On
INDICATOR
LEDS
OFF
Intermittent ON
Intermittent and Exchange ON
Continuous and Exchange ON
Continuous and Exchange ON
Recirculation ON
Recirculation and Exchange ON
Maintenance (open door)
TRIPLE-PANE
WINDOWS
65 percent
55 percent
45 percent
45 percent
35 percent