Functions

This chapter describes the various menus of the transmitter in details. The menu diagrams
are shown in appendix menu diagrams (Page 73).
8.1

Output settings

Three outputs are available:
● Current output (range and time constant); terminals 31 and 32.
● Digital output (pulse, frequency, error, limit, or batch settings); terminals 56, 57, and 58.
● Relay output (error, limit, and batch settings); terminals 44, 45, and 46.
Current output
In the current output menu it is possible to select current output range and time constant, see
also Current output menu diagram (Page 79).
If current output is set to "4-20 mA+Alarm", the current output will show the following mA:
● 1.3 mA (if error level is "Fatal").
● 2 mA (if error level is "Permanent").
● 3 mA (if error level is "Warning").
For setting of error level, see error level menu diagram (Page 80).
If current output is not used, it must be set to "Off".
Digital output
Digital output can be used to configure various settings:
● Pulse (volume/pulse, pulse output, pulse width, pulse polarity, and time constant), see
● Frequency (frequency output, max frequency, and time constant), see frequency menu
● Error settings (level and number), see error level menu diagram (Page 80) and error
SITRANS F M MAG 5000/6000
Operating Instructions, 01/2010, SFIDK.PS.026.G1.02
pulse menu diagram (Page 79).
diagram (Page 80).
number menu diagram (Page 80).