Installation
TABLE IV – Error Code Displays (LEDs Flashing)
LED Error Code Display
System Alert
Silenced audible alarm
Pump status
AC power
*
NOTE: If your AC power is off and the unit is dead (no LEDs lighted, no audible alarm, pump isn't running),
check for reversed battery connections to the charger/controller.
**
Charger was charging at a very low level to try to bring a dead battery back to life, but the battery took too long
to charge. Try resetting the charger once or twice (push the 'System Test' and 'Silence Alarm' buttons at the same
time to reset the charger).
***
Thermal Runaway condition
=
LED is ON Continuously
TABLE V – Control Button Functions
Control Button:
System Test
Silence Alarm
Flood Light
TABLE VI – Capacity Ratings with a 100 A-H Deep Cycle Marine Battery
Gallons Per Hour
Aproximate Hrs Available
Total Gallons Pumped
* These flow rates were obtained with a constant 12.7 VDC battery source. The actual GPH will vary due to a reduction in
output voltage from the battery as it discharges.
For parts or assistance, call Simer Customer Service at
Error Condition and Corrective Action
NOTE: When the 'System Alert' LED is flashing,
look for one of the following error conditions.
Charging
Battery status
Condition
= Excessive battery drain;
= Battery will not take a charge***;
= Reversed battery connections;
= Wrong battery voltage;
= Failed pre-qualification test – 1**;
= Failed pre-qualification test – 2**;
= Charge time monitor – 1;
= Charge time monitor – 2;
= Battery Charge is Below 20%;
=
LED is Flashing (Fast)
Result of Pushing Button:
Pump starts and all LEDs light up.
Will reset the 'Pump Status' LED.
When pushed with the 'Silence Alarm' button, the Charger/Controller
microprocessor resets and error code resets.
Toggle; Prevents the audible alarm sounding. Press and release to reset.
Toggles the flood light on the Charger/Controller on and off.
VERTICAL PUMPING DISTANCE - MODEL A5000-04
8 FEET (2.4 M)
10 FEET (3.0 M)
1,440
1,200
10
11.5
8,500
7,000
Action
Stop pump, allow battery to charge (AC must be on)
Replace battery with a new 12V lead-acid battery
Connect + to + and – to –.*
Replace battery with a new 12V lead-acid battery
Replace battery with a new 12V lead-acid battery
Replace battery with a new 12V lead-acid battery
Check battery for damage to cells; replace battery
Check battery for damage to cells; replace battery
Pump will shut down, battery is not charging. Replace
battery.
=
LED is Flashing (Slow)
12 FEET (3.7 M)
16 FEET (4.9 M)
840
No Flow at this Height
13
5,000
1-800-468-7867 / 1-800-546-7867
10
=
LED is OFF
5766 0108