This section provides rough guidelines for the block-out slot
size for 42S units with risers included. Therefore, the floor
block-out slot dimensions listed in this document should be
considered estimates. The engineer for the project is ultimate-
ly responsible for the actual dimensions and meeting local
code requirements.
To select using the following Tables A-D, locate the appropri-
ate unit size in the cabinet charts (dimensions are given in
inches). Then, follow the row across to locate the clear height
(If the clear height exceeds 96-in. use the 96-in. block-out
size). Under type of installation, read the block-out size. If the
clear height is lower than listed or is not recommended (NR)
in the standard 88-in. cabinet chart, use the short 79-in. cabi-
net chart. If the clear height is lower than listed or is not rec-
ommended (NR) in the short 79-in. cabinet chart, please con-
tact the factory.
For examples of clearance height, unit placement, and riser
length see Fig. A. For possible piping arrangements of the
42SJ unit see Fig. B.
Table A — STANDARD 88-IN. CABINET, TWO-PIPE
UNITS
BLOCK-OUT CONSTRUCTION SIZE
TYPE 1
CLEAR
UNIT SIZE
HEIGHT
(in.)
W x L (in.)
Single Unit and Siamese Back-to-Back
96
5
95
6
94
6
03, 04
93
92
7
96
6
95
6
06, 08
94
7
93
7
96
7
95
7
10, 12
94
42SJ Back-to-Back
93 and
03, 04
above
Not recommended for
93 and
standard 42SJ. For Sia-
06, 08
above
mese 42SJ use Single
93 and
10, 12
above
* Not recommended for Siamese Back-to-Back Installation.
NOTES:
1.
CLEAR HEIGHT is the dimension from the floor to ceiling (See
Fig. A of this appendix).
2.
The above charts allow 1-in. tolerance in clear height to allow for
variance in floor-to-floor dimensions.
3.
Consult factory for applications with 3-in. and 4-in. risers and insu-
lations exceeding
3
/
-inch.
4
4.
See Figure B for 42SJ unit and piping arrangements.
APPENDIX A — BLOCK-OUT CONSTRUCTION
TYPE OF INSTALLATION
TYPE 2
TYPE 3*
W x L (in.)
W x L (in.)
7
1
/
x 15
5
/
x 15
8
8
1
/
x 15
5
3
/
x 15
4
8
5 x 15
5
/
x 15
5
5
/
x 15
8
8
7 x 15
NR
1
/
x 15
NR
2
1
/
x 18
4
5
3
/
x 18
8
3
/
x 18
4
5 x 18
1
/
x 18
8
NR
5
/
x 18
8
1
1
/
x 22
5
/
x 18
2
8
1
/
x 22
5 x 22
2
NR
8 x 22
5 x 15
5 x 18
unit guidelines.
5 x 22
Table B — SHORT 79-IN. CABINET, TWO-PIPE
CLEAR
UNIT SIZE
HEIGHT
(in.)
Single Unit and Siamese Back-to-Back
91
90
03, 04
89
88
91
90
06, 08
89
88
91
90
10, 12
89
88
42SJ Back-to-Back
88 and
03, 04
above
88 and
06, 08
above
88 and
10, 12
above
* Not recommended for Siamese Back-to-Back Installation.
NOTES:
1.
CLEAR HEIGHT is the dimension from the floor to ceiling (See
Fig. A of this appendix).
2.
The above charts allow 1-in. tolerance in clear height to allow for
variance in floor-to-floor dimensions.
3.
Consult factory for applications with 3-in. and 4-in. risers and insu-
3
lations exceeding
/
4.
See Figure B for 42SJ unit and piping arrangements.
29
UNITS
BLOCK-OUT CONSTRUCTION SIZE
TYPE OF INSTALLATION
TYPE 1
TYPE 2
W x L (in.)
W x L (in.)
4
1
/
x 15
4
1
/
x 15
8
4
5 x 15
4
1
/
x 15
2
5
1
/
x 15
4
5
/
x 15
8
8
5
1
/
x 15
5 x 15
8
5 x 18
4
1
/
x 18
4
5
1
/
x 18
4
1
/
x 18
8
2
5
1
/
x 18
4
5
/
x 18
8
8
6
1
/
x 18
5 x 18
8
5
1
/
x 22
4
1
/
x 22
8
4
6 x 22
4
1
/
x 22
2
6
1
/
x 22
4
5
/
x 22
8
8
7 x 22
5 x 22
Not recommended for
standard 42SJ. For Sia-
mese 42SJ use Single
unit guidelines.
-inch.
4
TYPE 3*
W x L (in.)
5 x 15
5 x 18
5 x 22
5 x 15
5 x 18
5 x 22