Fm Class I, Ii, Iii, Div 1 Approval - Siemens SITRANS MAG 6000 I Operating Instructions Manual

Electromagnetic flowmeters
Hide thumbs Also See for SITRANS MAG 6000 I:
Table of Contents

Advertisement

Safety notes
2.3 Installation in hazardous area
2.3.3

FM Class I, II, III, Div 1 approval

Compact version for MAG 3100/3100 P sensors DN 15 to 300 (½" to 12")
Hazardous area
Class I, Div. 1, Group A, B, C, D
User I/O interface
Passive current
Active current
(31, 32)
(31, 32)
ABCD
U
28 V DC
U
i
O
I
100 mA
I
I
O
C
19.7 nF
C
I
O
L
36 µH
L
I
O
P
0.7 W
P
I
O
Notes from control drawing
1. The non-intrinsically safe terminals (power rail) must not be connected to a device which
uses or generates more than 250/30 Vrms or DC.
2. The installation must meet the requirements of the National Electrical Code/Canadian
Electrical Code.
3. Conduit seal is required within 460 mm (18") from MAG 6000 I in hazardous areas (Class
I, Div. 1).
The control drawings are found on the CD-ROM shipped with the device and on the Siemens
homepage at http://www.siemens.com/flowdocumentation.
See also
Control drawing (Page 97)
18
CD
AB
30 V DC
30 V DC
87.8 mA
86.8 mA
557 nF
63 nF
18.4 mH
4.6 mH
0.66 W
0.66 W
Relay
Frequency/pulse
(44, 45, 46)
(56, 57)
ABCD
ABCD
U
30 V DC
U
28 V DC
i
i
I
200 mA
I
100 mA
I
I
C
3.3 nF
C
14.2 nF
I
I
L
0 µH
L
36 µH
I
I
P
1.2 W
P
1.2 W
I
I
Profi (FISCO)
(95, 96)
ABCD
U
17.5 V DC
i
I
380 mA
I
C
0 nF
I
L
0 µH
I
P
5.32 W
I
SITRANS MAG 6000 I/6000 I Ex de
Operating Instructions, 08/2018, A5E02083319-AH
Digital input
(77, 78)
ABCD
U
30 V DC
i
I
I
C
0 nF
I
L
0 µH
I
P
1.2 W
I

Advertisement

Table of Contents
loading

Table of Contents