9.2

Common Technical Specifications

Important for the USA and Canada
The following approvals have been issued:
Address range
Supply voltage L+
rated value
ripple V
pp
permissible range (including ripple)
reference potential
Voltage for the isolated enable inputs (only required when enable
jumper is inserted)
Line lengths for
Analog input modules with rated input range of
12.5 m,
50 mV and Pt 100
Analog input modules with rated input range of
1 /
5 /
10 V /
20 mA, 4 to 20 mA and Pt 100
Analog output modules
Temperature range
in operation
for storage ans transportation
Relative humidity
Site altitude
Dimensions (W x H x D)
Weight
System Manual
C79000-G8576-C199-06
UL Listing Mark
Underwriters Laboratories (UL) to Standard UL 508, Report E 85972 and
E116536 for the 466-7LA11 analog input module
CSA Certification Mark
Mark Canadian Standard Association (CSA) to Standard C 22.2 No. 142,
Report LR 63533C and LR 48323 for the 466-7LA11 analog input
module
500 mV /
Analog Input/Output Modules
128 to 255 (0 to 255)
24 V
3.6 V
20 to 30 V
L–= M
= 0 V
ext
F+ = + 24 V
F– = 0 V
50 m max. for shielded cables laid separately
from power system cables (see Chapter 3)
200 m max., shielded
200 m max., shielded
o
0 to 55
C
o
– 40 to 70
C
o
95 % max. at 25
C, no condensation
3500 m max. above sea level
20 x 255 x 195 mm
Approx. 0.4 kg