Pre-Start And Start-Up - Bryant 581J-04A Installation Instructions Manual

Single package rooftop gas heat/electric cooling unit with puron (r-410a) refrigerant
Hide thumbs Also See for 581J-04A:
Table of Contents

Advertisement

BELT DEFLECTION FORCE (LBS)
BELT
SMALLEST
UNNOTCHED
CROSS
SHEAVE
SECTION
DIAMETER
USED
3.0-3.6
3.7
A, AX
3.8-4.8
4.5
5.0-7.0
5.4
3.4-4.2
B, BX
4.4-5.6
5.3
5.8-8.6
6.3
Table 1
BELT CONDITION
TENSION FORCE IN BELT (LBS)
New
Used
Table 2
Fig. 66 — V-Belt Force Label
NOTCHED BELTS
BELTS
NEW
USED
NEW
5.5
4.1
6.1
6.8
5.0
7.4
8.0
5.7
8.4
4.9
7.2
7.9
7.1
10.5
9.4
8.5
12.6
100
80
BELT TENSION METHOD — Requires
gauge that measures tension in belt in units of lbs force.
MOUNTING
BOLTS (4)
Fig. 67 — Belt Drive Motor Mounting
Pre-Start and Start-Up —
cal installation of the unit. Refer to the unit's Service Manual
for detailed Pre-Start and Start-Up instructions. Download the
latest versions from HVAC Partners (www.hvacpartners.com).
48
belt
tension
BLOWER PULLEY
V-BELT
MOTOR
PULLEY
MOTOR
MOTOR MOUNTING
PLATE
This completes the mechani-