NOTES
1. All wiring must be in accordance with
Article 760 of NEC or local building
codes. Wiring for each zone must be
Class B.
2. All output circuits are power limited
to NFPA 70 per NEC 760.
3. Electrical Ratings:
Output Zone Supervisory:
8mA max @ 24VDC
Output Zone Active:
25V — 25 watts max / zone
70V — 30 watts max / zone
4. EOL resistor, 24k ohms, 1 watt , 5%,
P/N 140-033771.
5. Polarity shown in active state.
6. For a list of Compatible Notification
Appliances, refer to P/N 315-096363.
7 . Refer to CAB1/CAB1R (P/N 315-
0330007) and CAB2-BB/CAB3-BB
(P/N 315-033009) Installation
Instructions for details on the
separation of power limited and
non-power limited wiring.
8. Positive and negative ground fault
detected at <40K for terminals 1 - 16.
STYLE Y
(CLASS B)
ZONE 5
24K,
1W
5%
STYLE Y
(CLASS B)
ZONE 6
24K,
1W
5%
CHANNEL A
TO NEXT
ZIC-8B
CHANNEL B
Figure 7
ZIC-8B Two-Channel Audio Wiring
(Requires ZIC-2C Board)
Siemens Industry, Inc.
Building Technologies Division
ZONE 1
ZONE 2
ZONE 3
STYLE Y
STYLE Y
STYLE Y
CLASS B
CLASS B
CLASS B
24K,
24K,
24K,
1W
1W
1W
5%
5%
5%
1
2
3
4
5
6
9
10
11
12
13
ONE SLOT OF CC-5
17
18
19
20
21
11
ZONE 4
STYLE Y
CLASS B
24K,
1W
5%
7
8
14
15
16
22
23
24
AUDIO FROM PREVIOUS
ZIC-8B OR ZIC-4A OR
FROM ZAC-40/ZAM-180
TERMINALS 1A AND 1B
OR 2A AND 2B
STYLE Y
ZONE 8
(CLASS B)
24K,
1W
5%
STYLE Y
ZONE 7
(CLASS B)
24K,
1W
5%
P/N 315-048670-11