Sensor Check Error Code Display; Displaying Error Content; Indoor Unit Error Display; Displaying Outdoor Unit Error - LG MULTI V MINI ARUN047GS2 Installation Manual

Hide thumbs Also See for MULTI V MINI ARUN047GS2:
Table of Contents

Advertisement

Sensor Check Error Code Display

Error display during sensor inspection process is composed of 3 stages as shown below, and is proceeded by repeating
these stages
n Step 1 : Display of error existence : 309 or 319
- 309 : Inspect sensors of outdoor unit
- 319 : Inspect sensors of indoor unit
n Step 2: Display of error location
- In case of 309 (outdoor unit sensors)
2 digits on the left among 7 segments – Sensor Type (Table1)
1 digit on the right among 7 segments – Outdoor Unit Number
- In case of 319 (indoor unit sensors)
2 digits on the left among 7 segments – Indoor Unit Number
1 Digit on the right among 7 segments – Sensor Type (Table 2)
n Step 3: Turn Off
h 1 error is displayed through 3 stages above and maximum of 5 errors are displayed.

Displaying error content

■ Indoor unit error display

1. 1
st
and 2
nd
number represents indoor unit number.
Indoor unit number follows auto addressing number.
2. Last number represents sensor.
1
Pipe inlet temperature sensor
2
Pipe outlet temperature sensor
3
Air temperature sensor
❈ Indoor unit number follows Auto addressing number.

■ Displaying outdoor unit error

1. 1
st
and 2
nd
number represents error content(code).
2. Last number represents outdoor unit number.
1
Outdoor Air Temperature
2
Heat Exchanger 1
4
Inverter Compressor Discharge Temperature
6
Suction Temperature
7
Liquid Pipe Temperature
9
SC pipe out
10
High Pressure Sensor
11
Low Pressure Sensor
CAUTION
1. Up to 5 number of errors is displayed continuously and repeatedly. In case 5 number of errors occurs, again perform
sensor checking after solving errors.
2. IDU in which error occurred operates air circulation mode.
(Same as LGMV (automatic address configuration) indoor unit number)
ex) Indoor unit No. 2 pipe inlet temperature sensor
error
ex) Outdoor unit liquid pipe temperature
sensor error
ex) Indoor unit No.2 pipe inlet temperature sensor error and
outdoor unit suction temperature sensor error