The Procedure Of Automatic Addressing - LG MULTI V MINI ARUN047GS2 Installation Manual

Hide thumbs Also See for MULTI V MINI ARUN047GS2:
Table of Contents

Advertisement

Electrical Wiring
u The Procedure of Automatic Addressing
Power On
Waiting 3 minutes
Press SW02V for 5 sec.
7-segment LED
Waiting about 2~7 minutes
7-segment LED
= 88
YES
OK
50
Outside Unit
All DIP switch should be off before auto adressing
Auto addressing start
= 88
• Auto addressing setting end
Numbers of indoor unit connection set whose
addressing is completed are indicated for 30seconds
on 7-segment LED after completing setting
NO
Indoor address number is displayed on wired remote control or
indoor unit display window. It is not an error message, will
disappeared when on/off button is pressed on remote control
ex) Display of 01, 02, ..., 15 means connection of 15 indoor
units and auto addressing is completed normally.
Check the connections
of communication line