Siemens CP 1243-1 PCC Operating Instructions Manual page 53

Telecontrol
Table of Contents

Advertisement

The method is explained based on the following example in which a threshold value of 2.0 is
configured.
Table 5- 4
(calculation cycle)
In this example, a value of 2.0 was configured for the threshold value trigger.
With the changes in the process value shown in the example, the threshold value trigger
fires twice, if the value 2.0 is reached:
● At the time 3.5 s: The value of the integrated deviation is at 2.0. The new process value
stored in the send buffer is 20.5.
● At the time 6.0 s: The value of the integrated deviation is at 2.1. The new process value
stored in the send buffer is 19.9.
In this example, if a deviation of the process value of approximately 0.5 should fire the
trigger, then with the behavior of the process value shown here a threshold value of
approximately 1.5 ... 2.5 would need to be configured.
Siemens Automation
CP 1243-1 PCC
Operating Instructions, 02/2015, C79000-G8976-C384-01
Example of the integration calculation of a threshold value configured with 2.0
Time [s]
Process value
stored in the
send buffer
0
20.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
20.5
4.0
4.5
5.0
5.5
6.0
19.9
5.11 STEP 7 configuration of individual parameters
Current process
Absolute deviation
value
from the stored
20.0
20.3
19.8
20.2
20.5
20.3
20.4
20.5
20.4
20.1
19.9
20.1
19.9
Configuration and operation
Integrated devia-
tion
value
0
0
+0.3
0.3
-0.2
0.1
+0.2
0.3
+0.5
0.8
+0.3
1.1
+0.4
1.5
+0.5
2.0
-0.1
-0.1
-0.4
-0.5
-0.6
-1.1
-0.4
-1.5
-0.6
-2.1
53

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic s7-1200

Table of Contents