Outdoor Fan; Electrical Controls And Wiring; Refrigerant Circuit - International comfort products PDS4 Installation Instructions Manual

Category i gas heating/electric heating and cooling unit designed for outdoor installation.
Table of Contents

Advertisement

between the coils. Be sure to flush all dirt and debris from the unit
base.
Inspect the drain pan and condensate drain line when inspecting
the coils. Clean the drain pan and condensate drain by removing all
foreign matter from the pan. Flush the pan and drain tube with
clear water. Do not splash water on the insulation, motor, wiring, or
air filter(s). If the drain tube is restricted, clear it with a "plumbers
snake" or similar probe device. Ensure that the auxiliary drain port
above the drain tube is also clear.
Fig. 20 - - Removal of Motor and Blower Wheel
Fig. 21 - - Burner Rack Removed
FEEDER TUBE
Fig. 22 - - Defrost Thermostat Location
51801230403

Outdoor Fan

BLOWER
HOUSING
2 SETSCREWS
(HIDDEN)

Electrical Controls and Wiring

Inspect and check the electrical controls and wiring annually. Be
sure to turn off the gas supply, and then the electrical power to the
unit.
Remove access panels (see Fig. 19) to locate all the electrical
controls and wiring. Check all electrical connections for tightness.
C99085
Tighten all screw connections. If any discolored or burned
connections are noticed, disassemble the connection, clean all the
parts, re- -strip the wire end and reassemble the connection properly
and securely.
After inspecting the electrical controls and wiring, replace the
access panels (see Fig. 19). Start the unit, and observe at least one
complete heating cycle and one complete cooling cycle to ensure
proper operation. If discrepancies are observed in any operating
cycle, or if a suspected malfunction has occurred, check each
electrical component with the proper electrical instrumentation.
Refer to the unit wiring label when making these checkouts.
NOTE: Refer to the heating and/or cooling sequence of operation
in this publication as an aid in determining proper control
operation.

Refrigerant Circuit

Annually inspect all refrigerant tubing connections.
A07680
STUB TUBE
If low cooling performance is suspected, leak- -test all refrigerant
tubing using an electronic leak- -detector, halide torch, or
DEFROST
liquid- -soap solution. If a refrigerant leak is detected, refer to the
THERMOSTAT
Check for Refrigerant Leaks section.
C99029
If no refrigerant leaks are found and low cooling performance is
suspected, refer to the Checking and Adjusting Refrigerant Charge
section.
Specifications are subject to change without notice.
CAUTION
!
UNIT OPERATION HAZARD
Failure to follow this caution may result in damage to unit
components.
Keep the outdoor fan free from all obstructions to ensure
proper cooling operation. Never place articles on top of the
unit.
1. Remove 6 screws holding outdoor grille and motor to top
cover.
2. Turn motor/grille assembly upside down on top cover to
expose the fan blade.
3. Inspect the fan blades for cracks or bends.
4. If fan needs to be removed, loosen the setscrew and slide the
fan off the motor shaft.
5. When replacing fan blade, position blade back to the same
position as before.
6. Ensure that setscrew engages the flat area on the motor shaft
when tightening.
7. Replace grille.
WARNING
!
EXPLOSION,
PERSONAL
ENVIRONMENTAL HAZARD
Failure to follow this warning could result in personal injury,
death or property damage.
System under pressure. Relieve pressure and recover all
refrigerant before system repair or final unit disposal. Use all
service ports and open all flow- -control devices, including
solenoid valves.
INJURY
AND
51

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

E seriesPdd4

Table of Contents