Friedrich MD24Y3J Svc Manual page 6

Single zone air conditioner
Hide thumbs Also See for MD24Y3J:
Table of Contents

Advertisement

1.2 Inspections after Repair
Check to see if the power cable is not dirty or loose. If the plug is dusty or
loose it can cause an electrical shock or fire.
Do not use a spliced power cable or extension cable, or share the same power
outlet with other electrical appliances. otherwise, it can cause an electrical shock,
excessive heat generation or fire.
Do not insert hands or other objects through the air inlet or outlet while the prod-
uct is operating. There are sharp and moving parts that could cause personal
injury.
Do not block the inlet or outlet of air flow. It may cause product failure
Check to see if the parts are mounted correctly and wires are connected.
Improper installation and connections can cause an electric shock or an injury.
Check the installation platform or frame has corroded. Corroded installation plat-
form or frame can cause the unit to fall, resulting in injury.
Be sure to check the earth wire is correctly connected.
After the work has finished, be sure to do an insulation test to check that
resis-tance is 2[Mohm] or more between the charge section and the non-charge
metal section (Earth position). If the resistance value is low, a disaster such as a
leak or electric shock is caused at user's side.
Check the drainage of the indoor unit after the repair. If drainage is faulty
water may enter the room and wet floor.
Only for training and service purposes
- 6 -

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Md36y3jMc24y3jMc36y3jMr24uy3jMr36uy3j

Table of Contents