Endura AZ series integral and remote transmitter
Combustion oxygen monitor
Parameter
...Input/Output
Current Output 2
Elec. Range Hi
mA
Elec. Range Lo
mA
Output Failure
Disabled
Enabled
Failure Current
Output #2 Test
Table 5.12 Input/Output Menu (Continued)
60
Comment / [Range]
Displayed only if an option board is fitted.
Selects the electrical range high current output value.
[0.00 to 22.00 mA]
Selects the electrical range low current output value.
[0.00 to 22.00 mA]
When 'Enabled', the current output can be driven to a
preset value if a Failure category diagnostic state
occurs – see Section 8.1, page 78.
Sets a preset value that the current output is driven to
when a Failure category diagnostic state is present –
see page 78.
Only available if Output Failure is Enabled.
[0.00 to 22.0 mA]
Selects % output levels for Current Output 2.
When this parameter is exited, the current output
returns to its normal operating value.
[0, 25, 50, 75 or 100 %]
5 Programming
Default
20.00 mA
4.00 mA
Disabled
22.00 mA
0
IM/AZ20E–EN Rev. F