Mounting the IED

Required tools

T25 Torx screwdriver for mounting the case
T20 Torx screwdriver for connecting the protective grounding
Only use adjustable torque screwdrivers.

Flush mounting the IED

All the mounting elements are integrated in the IED.
Requirements for installation:
Panel cut-out of 9.76 x 6.38 inches (248 x 162 mm)
Depth behind the panel 6.02 inches (153 mm)
An IED equipped with optic connections requires a minimum depth of
7.09 inches (180 mm). The allowed minimum bending radius has to be
checked from the optical cable manufacturer.
1.
Loosen the four M5 fixing screws in the case to fit the case into the panel cut-out.
2.
Mount the case to the panel cut-out.