Potterton Eurocondense five 125 kW Installation Manual page 65

Gas condensing boiler
Table of Contents

Advertisement

Boiler
Pump modulation
0: None | 1: Demand | 2: Boiler setpoint | 3: Temp differential nominal | 4:
Burner output
Pump speed min
Pump speed max
Output nominal
Output basic stage
Output at pump speed min
Output at pump speed max
Fan output heating max
(1)
Fan output full charging max
(1)
Fan output DHW max
Controller delay
0: Off | 1: Heating mode only | 2: DHW mode only | 3: Heating and DHW mode
7703301 - 01 - 16072018
(1)
Prog. no.
Level
Standard value
2320
E
3: Temp differential
nominal
2322
E
30%
2323
E
100%
2330
E
EC five 125 kW: 125
kW
EC five 170 kW: 170
kW
EC five 215 kW: 215
kW
EC five 260 kW: 260
kW
EC five 300 kW: 300
kW
2331
E
EC five 125 kW: 20
kW
EC five 170 kW: 28
kW
EC five 215 kW: 35
kW
EC five 260 kW: 42
kW
EC five 300 kW: 48
kW
2334
E
10 %
2335
E
90 %
2441
E
EC five 125 kW: 125
kW
EC five 170 kW: 170
kW
EC five 215 kW: 215
kW
EC five 260 kW: 260
kW
EC five 300 kW: 300
kW
2442
E
EC five 125 kW: 125
kW
EC five 170 kW: 170
kW
EC five 215 kW: 215
kW
EC five 260 kW: 260
kW
EC five 300 kW: 300
kW
2444
E
EC five 125 kW: 125
kW
EC five 170 kW: 170
kW
EC five 215 kW: 215
kW
EC five 260 kW: 260
kW
EC five 300 kW: 300
kW
2450
E
1: Heating mode only
9 Settings
65

Advertisement

Table of Contents
loading

Table of Contents