Weil-McLain Series 2 Manual page 112

Wall mount gas-fired water boilers
Hide thumbs Also See for Series 2:
Table of Contents

Advertisement

®
S
ERIES
Cleaning heat exchanger flue side, 155
DO NOT gouge or crack the refractory. The refractory
is made of ceramic fiber materials. Read the ceramic
fiber WARNING on page 89 before handling or
disposing of ceramic fiber materials.
c. When replacing the refractory, apply a ring of silicone
adhesive on the cover plate. Place the refractory onto the
cover plate. Before handling the assembly, allow the adhesive
to set enough that the refractory is firmly held in place.
2. Clean the burner gasket surface inside the heat exchanger cover
plate (item 6) with a soft brush to remove any gasket residue.
3. The burner gasket must be replaced with a new one when the boiler
is re-assembled after servicing.
Inspect and clean the heat exchanger
1. Access the heat exchanger interior by following the previous
instructions. Remove and inspect the heat exchanger cover plate
gasket. Replace if necessary.
2. See Figure 117, page 113 part E.
3. Before using water to clean the heat exchanger, remove the control
module (item 17). Label wires if they are not labeled. Set aside.
Remove all connectors and wire harnesses from the control module
and then remove the two screws securing it to the bracket.
4. Use a strong light to visually inspect the interior of the heat
exchanger. Make sure the flue ways (tubes) are clear and
unobstructed.
5. Use a vacuum cleaner to remove any accumulation on the heating
surfaces. This includes removing any pieces of refractory that may
have dropped into the exchanger.
DO NOT use any solvent when cleaning the
exchanger.
6.
If the vacuum cleaner is unable to clean completely, wash the
heating surfaces with clean, warm water.
a. Place a bucket under the boiler condensate drain connection.
b.
Loosen and move the condensate bracket, then loosen the
condensate trap upper nut and slide the trap off of the
drain connection.
(See Figure 65, page 58 for reference.)
c. Spray fresh water into the heat exchanger and tubes to
remove sediment. Collect water in the bucket below.
7. Inspect the heat exchanger cover plate gasket (item 18). Replace if
is damaged in any way.
Reinstalling ECO 155 components
1. See Figure 117, page 113 for reference.
2. Reinstall the control module (item 20) to the control bracket and
reconnect all connectors and wire harnesses.
3. Reinstall the burner (item 11), burner gasket (item 12) and burner
access cover seal (item 13) on the heat exchanger cover plate (item 6).
a. Insert and tighten the burner cover plate screws and
washers (item 10) using a Phillips screwdriver. The screws
must be secure, with torque no more than 20 inch-pounds.
4. Reinstall the heat exchanger cover plate assembly on the heat
exchanger.
a. Seat the heat exchanger cover plate gasket on the heat exchanger
sealing surface.
b. Tilt heat exchanger cover plate front lip downward until back lip
clears cabinet and burner can slide inside combustion chamber.
Slide cover plate back and rotate until seated flat on the heat
112
2
-
G
AS
FIRED WATER BOILER
— Boiler Manual
Figure 116
Legend for Figure 117, page 113
Boiler interior
A
B Assembled heat exchanger
cover plate (item 6),
burner (item 11), showing
refractory (item 15)
C Disassembly of heat
exchanger cover plate,
burner and other
components
D Burner assembly
E Heat exchanger interior
1 Inlet air silencer
2 Blower assembly
3 Gas valve
4 Burner access cover
5 Venturi assembly
6 Heat exchanger cover plate
7 Igniter assembly
exchanger sealing surface. Avoid gouging the refractory on
the heat exchanger studs.
c. Secure the heat exchanger cover plate (item 6) to the heat
exchanger with the five (5) M6 nuts using a 10mm wrench.
You must gradually tighten the cover plate nuts using
a torque wrench. The final torque MUST NOT exceed
45 inch-pounds. Alternate tightening until all nuts
reach 45 inch-pounds.
5. Reinstall the blower/gas valve/venturi assembly (items 2, 3, and 5).
a. Place blower flange on to studs protruding from cover plate.
b. Reinstall the two (2) 5/16" locknuts using a socket with
extension.
c. Do not over tighten (torque no more than 20 inch-pounds).
6. Reinstall the igniter assembly (item 7).
a. The igniter gasket must be intact and in good condition.
Replace with a new gasket if necessary.
b. Insert the igniter into the cover plate opening, with the
gasket in position.
c. Reinstall the two (2) Socket head Allen bolts finger tight.
d. Use a torque wrench to tighten the igniter screws.
DO NOT exceed 25 inch-pounds torque.
e. Reconnect the ignition cable and the igniter ground wire.
7. Reconnect the flexible gas line to the gas valve using two wrenches.
8. Reinstall the air inlet silencer (item 1) by pressing up onto the
venturi (item 5). Rotate the air silencer clip (item 8) and snap it
onto the gas line.
9. Reconnect the two (2) wire harnesses to the blower and gas valve.
10. Reinstall the condensate trap and bracket on the boiler
condensate drain connection. (See Figure 65, page 58 for
reference.)
Perform a complete start-up procedure when putting
the boiler back into service. See page 79 and all
instructions for start-up and verification. Include a
soap suds leak test on all interior and exterior gas
piping after starting the boiler.
(continued)
8 Air silencer clip
9 Heat exchanger cover plate
retainer nuts, (5)
10 Burner cover retainer (3)
screws, M4 Phillips plus flat
washers
11 Burner
12 Burner gasket
13 Burner access cover seal
14 Burner sealing surface
(lower surface of burner
flange)
15 Refractory
16 Cover plate gasket
17 Control module
18 Heat exchanger tube sheet
19 Heat exchanger outer shell
Part number 550-142-190/1218

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Eco 110Eco 155Eco 70

Table of Contents