charge. Replace the battery if it will not maintain a
charge.
4. Clean and wipe down the entire generator.
5. Verify that the 7.5 amp fuse is removed from the
generator control panel.
6. Reconnect the battery. Observe battery polarity.
Damage may occur if the battery is connected
incorrectly. Install positive cable first.
7. Reconnect the battery charger AC input T1/Neutral
cable (white sleeve) at controller.
8. Open the fuel shutoff valve.
9. Insert the 7.5 amp fuse into the generator control
panel.
10. Press the MANUAL button to start the unit. Allow
the unit to warm up for a few minutes.
11. Complete the Installation Wizard information.
12. Press the control panel OFF button to stop the unit.
13. Engage the connected loads to the generator.
14. Set the control panel to AUTO.
The generator is ready for service.
NOTE: The current date and time must be reset when a
battery is dead or has been disconnected.
Owner's Manual for 60 Hz EcoGen™ Generators
Maintenance
33