Electrical Data For Inputs And Outputs - ABB LME620-AI User Manual

Electronic unit for field installation for the control of contrac control actuators series pme, lme, rhd and rsd
Hide thumbs Also See for LME620-AI:
Table of Contents

Advertisement

LME620-AI / PME120-AI / EAN823 / EBN853 / EBN861 ELECTRONIC UNIT | OI/PME/LME/EAN823/EBN853/EBN861-EN REV. E

Electrical data for inputs and outputs

Power supply
PME120-AI / LME620-AI
Supply voltage
Current consumption at the electronic unit [A]
(AC 115 V / AC 230 V)
Actuators for low temperature design
External fuse
EBN853
Supply voltage (standard actuators)
Supply voltage (Ex actuators)
Current consumption at the electronic unit
(AC 115 V / AC 230 V)
External fuse for electronic unit
115 V AC (94 to 130 V) or 230 V AC (190 to 260 V); 47.5 to 63 Hz; single-phase
LME620-AI, PME120
l
at 115 V: 1.0 A
max
LME620-AI, PME120
l
at 115 V: 1.4 A
max
16 A; time-lag
115 V AC (94 to 130 V) or 230 V AC (190 to 260 V); 47.5 to 63 Hz; single-phase
115 V AC (94 to 127 V) or 230 V AC (190 to 253 V); 47.5 to 63 Hz; single-phase
Actuator
l
at 115 V
max
RHD(E)250-10
1.8 A
RHD(E)500-10
2.2 A
RHD(E)800-10
5.0 A
RHD(E)1250-12
5.0 A
RHD(E)2500-25
5.0 A
RHD(E)4000-40
5.8 A
RHD(E)8000-80
5.0 A
RSD(E)10-5,0
2.2 A
RSD(E)10-10,0
3.6 A
RSD(E)20-5,0
3.6 A
RSD(E)20-7,5
4.8 A
RSD(E)50-3,0
5.0 A
RSD100-1.5
5.0 A
RSD200-0.7
5.0 A
16 A; time-lag
l
at 230 V: 0.5 A
l
(115 V + 230 V):
max
pos
approx. 40 to 50 % of l
l
at 230 V: 0.7 A
max
l
at 230 V
l
(115 V + 230 V):
max
pos
approx. 40 to 50 % of l
0.9 A
1.1 A
2.5 A
2.5 A
2.5 A
2.7 A
2.5 A
1.1 A
1.8 A
1.8 A
2.4 A
2.5 A
2.5 A
2.5 A
25
max
max