Delivery Status - ABB LME620-AI User Manual

Electronic unit for field installation for the control of contrac control actuators series pme, lme, rhd and rsd
Hide thumbs Also See for LME620-AI:
Table of Contents

Advertisement

LME620-AI / PME120-AI / EAN823 / EBN853 / EBN861 ELECTRONIC UNIT | OI/PME/LME/EAN823/EBN853/EBN861-EN REV. E

Delivery status

The individual actuator configuration may vary from the
standard setup above. This information can be displayed via the
user interface.
Unless otherwise specified by the user, the electronic units are
delivered with the following standard configuration:
Conventional communication
Parameter
Function selection
Set point function
Set point range
Set point characteristic
Actual value range
Nominal torque / rated force in
±direction
Automatic speed in ±direction:
Action in 0 % / 100 % end
position
Digital inputs
Digital outputs
Brake Away Function
Shut-off function
Positioning loop monitoring
Set point monitoring
Alarm Type
Action after restoration of
power
Working range of actuator
Setting
Positioner, parameter: set point
Analog set point
4 to 20 mA
Linear; set point = position value
4 to 20 mA
100 %
100 %
Keep leak-tight with nominal torque / rated
force
Digital input 1 Manual / Automatic
switching,
Digital input 2 / 3 Travel command ±
Digital output 1 ready for operation / error
message,
Digital output 2 / 3 end position signaling
0 % / 100 %
Deactivated
Deactivated
Deactivated
Deactivated
Deactivated
Switch to Automatic
Not set
PROFIBUS DP® communication
Parameter
Function selection
Set point function
Set point range
Set point characteristic
Actual value range
Nominal torque / rated force in
±direction
Automatic speed in ±direction:
Action in 0 % / 100 % end
position
Digital outputs
Brake Away Function
Shut-off function
Positioning loop monitoring
Communication monitoring
Alarm Type
Action after restoration of
power
Working range of actuator
Setting
Positioner, parameter: set point
Digital
4 to 20 mA
Linear; set point = position value
Digital
100 %
100 %
Keep leak-tight with nominal torque / rated
force
Digital output 1 / 2 end position signal 0
% / 100 %
Deactivated
Deactivated
Deactivated
PROFIBUS DP® / V0:
Activated
Lock in last position
PROFIBUS DP® / V1:
Activated
After delay time has elapsed (standard
configuration 5 s)
Lock in last position
Deactivated
Switch to Automatic
Not set
11

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pme120-aiEan823Ebn861Ebn853

Table of Contents