Rheem RT1000C6 Owner's Manual And Installation Instructions page 5

Commercial carbon steel indirect storage tank
Table of Contents

Advertisement

Warning
This storage tank is only intended to be operated by persons who have the experience or the knowledge and
the capabilities to do so. This storage tank is not intended to be operated by persons with reduced physical,
sensory or mental capabilities i.e. the infirm, or by children. Children should be supervised to ensure they do
not interfere with the storage tank.
SAFETY
This storage tank is supplied with a combination temperature pressure relief valve. When installed as
instructed in this manual, this valve has a rating of 575 kW. If the primary heating source has an output
exceeding this valve, additional relief valves are required. The valve(s) must not be tampered with or
removed. The storage tank and its primary heating source must not be operated unless each of these
devices is fitted and is in working order.
This storage tank is designed to be used in a closed circuit. Supplementary pressure relief devices such
expansion vessels, permanently venting the cylinder or using as a drain back solar system must be included
in the system design.
If a remote thermostat (Tankstat) is fitted to the storage tank and the electrical conduit is damaged, it must be
replaced by a qualified person in order to avoid a hazard. Phone Rheem Service or their nearest Accredited
Service Agent to arrange for an inspection.
Warning: For continued safety of this water heating system it must be installed, operated and maintained
in accordance with the Owner's Guide and Installation Instructions.
The Rheem warranty may not cover faults if relief valves or other safety devices are tampered with or
if the installation is not in accordance with these instructions.
PRECAUTIONS
Where damage to property can occur in the event of the storage tank leaking, the storage tank must be
installed in a safe tray. Construction, installation and draining of a safe tray must comply with AS/NZS 3500.4
and all local codes and regulatory authority requirements.
The storage tank must be maintained in accordance with the Owner's Guide and Installation Instructions.
"Regular Care"
Refer to
on page 7.
If this storage tank is to be used where an uninterrupted hot water supply is necessary for your application or
business you should ensure that you have back up redundancy within the hot water system design. This
should ensure the continuity of hot water supply in the event that this storage tank were to become inoperable
for any reason. We recommend you seek advice from your plumber or specifier about your needs and
building back up redundancy into your hot water supply system.
TO TURN OFF THE STORAGE TANK
If it is necessary to turn off the storage tank:
Turn off the primary water heating plant and switch off the electrical supply at the isolating switch to the
circulating pump(s).
Close the cold inlet isolation valve on the cold inlet line to the storage tank(s) to shut down the entire
system, or;
Close the isolation valves on the cold, flow / return and hot branches to shut down an individual storage
tank in a bank.
TO TURN ON THE STORAGE TANK
Open the isolation valves fully on the cold, flow / return and hot water branches to the storage tank(s)
installed in a bank.
Open the cold inlet isolation valve on the cold inlet line to the storage tank(s). Air will be forced out of the
System.
Switch on the electrical supply at the isolating switch to the circulating pump(s) and turn on the primary
water heating plant.
ABOUT YOUR STORAGE TANK
5