Using The Icp-B6 As A Telephone Zone; Using The Icp-B6 As A 70 Volt Speaker Zone - Siemens ICP-B6 Installation Instructions Manual

Intelligent control point
Table of Contents

Advertisement

FROM MXL MMB OR
ALD-2I ON MOM-4
(12 MAX ICP-B6
MODULES PER LOOP)
ANALOG LOOP
(SUPERVISED)
CONNECTION
TB1
TO
EARTH
+
ICP-B6 DC SUPPLY
FROM MMB, PSR-1, OR
UL LISTED POWER SUPPLY
MANUFACTURED BY ALARM-SAF
-
Model BN4-002-UL (SUPERVISED)
NOTES:
1. THE SHIELD ON THE COMMON TALK LINE MUST BE CONTINUOUS
AND CONNECTED ONLY TO DC COMMON AT CONTROL PANEL.
2. ALL WIRING MUST CONFORM TO NATIONAL AND LOCAL CODES.
3. POSITIVE AND NEGATIVE GROUND FAULT DETECTED AT <5K OHMS FOR TERMINALS 3-6.

2. Using the ICP-B6 as a Telephone Zone

When the ICP-B6 is used as a telephone zone
module, the 24 VDC provides supervision,
trouble, and call-in conditions. If the 24 VDC is
lost, the trouble condition INPUT DEVICE
RESPONSE TOO LOW displays at the MXL/
MXLV and an LED for that zone lights at the
VSM-1 module.
The supervised telephone common talk riser
starts at the TBM module in the MME-3 back-
box. The Class B shielded cable connects
continuously to each ICP-B6 with a 5.6K end of
line device. Tie the shield of these riser wires
and the shield of the zone output wires together
using terminal 5 of TB2 and isolate them from
the system circuits and the earth ground.
Connect the supervised individual zone output
connections from each ICP-B6 to the field
telephone with shielded cable. Terminate
them at the last station with a 10K ohm end of
line resistor. As with the common talk line
described in the paragraph above, be sure
that the shield is continuous and isolated
SUPERVISED
POWER LIMITED
SHIELD
1
2
3
6
4
5
-
-
+
+
ICP-B6
JP2
PROGRAM
PLUG
JP1
- -
+
+
TB2
1
6
5
4
3
2
SHIELD
SHIELD
FROM PREVIOUS ICP-B6, OCC-1,
OR TBM
(20 OHMS MAXIMUM
LINE RESISTANCE)
COMMON TALK RISER
RISER
NOMINAL VOLTAGE:
17.5 VDC
MAXIMUM CURRENT:
175 mA
ICP-B6 Used as a Telephone Zone
SHIELD
SHIELD
TB1
1
2
3
4
FJ-303
-
+
+
ICP-B6
PROGRAM
PLUG
FJ-303
- -
TO
6
5
4
3
EARTH
SHIELD
5.6K, 1/2W, +/-5%
10K, 1/2W, +/-5%
EOL RESISTOR
P/N 140-112172
AT LAST FJ-303
ELECTRICAL:
INPUT DC SUPPLY:
SUPERVISORY OUTPUT:
ACTIVATED OUTPUT:
Figure 5
from both system circuits and earth
ground and that the shields are connected
together using terminal 5 of TB-2.
3. Using the ICP-B6 as a 70 Volt Speaker
Zone
When the ICP-B6 is used as a speaker zone,
the 24 VDC provides the supervision. If the 24
volts is lost or there is an open or shorted
speaker output line, the trouble condition
INPUT DEVICE RESPONSE TOO LOW
displays at the MXL/MXLV and the related
zone LED on the VSM-1 lights.
The 70.7V RMS audio input comes from the
amplifier via the ASC-2 Amplifier Supervision
card. The ASC-2 supervises the audio con-
nection path to the ICP-B6 and provides up to
100 watts of power. The ASC-2 can be used
as Style Y (Class B) or Style Z (Class A). Refer
to the ASC-2 Instructions, P/N 315-092085.
When the ICP-B6 is used as a speaker zone,
the output speaker lines are supervised and
power limited. The audio output cannot exceed
5
24 OHMS MAX
SHIELD
6
5
-
SHIELD
WARDEN'S STATIONS
JP2
MODELS FT-301 SERIES
AND FT-302 SERIES
JP1
+
+
TB2
1
2
10K, 1/2W, +/-5%
EOL RESISTOR
P/N 140-112172
AT LAST STATION
EOL RESISTOR
18 AWG MINUMUM
BELDON 8760 OR EQUIVALENT
OR AS REQUIRED BY
THE LOCAL AUTHORITY
HAVING JURISDICTION
20.5 TO 30 VDC, 18mA MAX
8V, .8mA
11V, 70mA
+
-
+
-
+
-
+
-