High-Speed Counter Specifications; Pwm Output/Pulse Train Output Specifications; Analogue Input Specifications - Hitachi HIDIC MICRO-EH Applications Manual

Table of Contents

Advertisement

3.3.4

High-Speed Counter Specifications

Available input
Input voltage
Count pulse width
Maximum count frequency
Count register
Coincidence output
On/Off-preset
Upper/lower limit setting
Preload/strobe
Since 10 points type does not have input X6, counter channel is up to 3 ch.
3.3.5

PWM Output/Pulse Train Output Specifications

Available outputs
Load voltage
Minimum load current
PWM max. output frequency *1
Pulse train max. output frequency *1
Pulse acceleration/deceleration
*1:
Relay outputs cannot keep up with high frequencies; these outputs should be used at the operating frequency upon confirmation.
3.3.6

Analogue Input Specifications

Module type
Input channel
Input range
Resolution
Accuracy
Linearity
Current input impedance
Voltage input impedance
Input delay time
Channel to internal circuit insulation
Channel-to-channel insulation
Single phase
X0, X2, X4, X6
ON
OFF
23-point and 28-point type
23 points module
0-10 V (10.24V max.)
0-20 mA (20.48 mA max.)
-
Approx. 100 kΩ
Chapter 3 Function and Performance Specifications
X0 and X2 in pair
15 V
5 V
100 µs
10 kHz each channel
16 bits
Allowed
Allowed
Not allowed
Allowed
Relay Output
Y100 (optional)
5/12/24 V
2 kHz total channels
5 kHz total channels
By FUN 151.
WX30, WX31
0-10V (10.24V max.)
-10 to +10V (±10.24V max.)
0-20 mA (20.48 mA max.)
4-20 mA (20.38 mA max.)
12 bits
±1 % of full scale
Max. +/-3 units
Approx. 249 Ω
20 ms
Not insulated
Not insulated
3-12
Two phase
10/14/28-point
Transistor Output
Y100-Y103 (optional)
12/24 V
1 mA
Analog exp. unit
WX u01 - WX u04
(u : unit number)
Approx. 200 kΩ
Insulated

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents