1.2 Standard Compliance

CE
RCM
CB Report (by TUV)
EN 62040-1
EN 62040-2 Category C1 [1kVA]
EN 62040-2 Category C2 [2kVA/3kVA]

1.3 Storage

Prior to installation
If the UPS needs to be stored prior to installation, it should be placed in a dry
area. The allowable storage temperature and relative humidity (non-condensing)
are -15°C ~+50°C and 5~95% respectively.
After usage
Press the
UPS is shut down, remove all equipment from the UPS, and store the UPS in a
dry and well-ventilated area at a temperature between -15°C and +50°C and at a
relative humidity (non-condensing) between 5~95%. Idle batteries must be fully
recharged every three months if the UPS needs to be stored for an extended
period of time. Whenever you recharge the batteries (internal and external),
please fully charge them until the Battery Level Bar Graph
UPS's LCD is fully on.
NOTE :
UPS to adjust to room temperature (20°C~25°C) for at least two hours to
avoid moisture condensing inside the UPS.
Amplon RT Series
button, disconnect the UPS from the utility power, make sure the
OFF
After storage and before start-up of the UPS, you must allow the
6
shown on the