1-1 Unit Specifications
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity*
Moisture removal (High)
Air circulation (H / M / L)
S.E.E.R. (H.S.P.F.)
ELECTRICAL RATINGS
Voltage rating
Available voltage range
Running amperes
Power input*
Maximum overcurrent protection
FEATURES
Controls
Low ambient control
Fan speeds Indoor / Outdoor
Optional Wired Remote Controller (Timer)
Optional Wireless Remote Controller (Timer)
Air deflection
Air filter
Operation sound
Refrigerant control
REFRIGERANT PIPING
Limit of piping length
Limit of piping length at shipment
Limit of elevation difference
between the two units
Refrigerant piping
Flare type
DIMENSIONS & WEIGHT
Unit dimensions
Indoor grille dimensions
Net weight
Shipping weight
Shipping volume
Cooling :
Rating conditions (*)
Heating :
Rating conditions (*)
Low temp conditions (**) : Room temperature 70 F DB / 60 F WB, Ambient temperature 17 F DB / 15 F WB
Indoor Unit
Outdoor Unit
BTU / h
(17 F)**
Pints / h
230 V
cu.ft. / min.
BTU / Wh
VAC
VAC
(17 F)**
Horizontal / Vertical
Indoor - Hi / Me / Lo
dB - A
Outdoor - Hi
dB - A
ft.
(m)
ft.
(m)
ft.
(m)
Narrow pipe
in. (mm)
Wide pipe
in. (mm)
Height
in. (mm)
Width
in. (mm)
Depth
in. (mm)
Height
in. (mm)
Width
in. (mm)
Depth
in. (mm)
lbs. (kg)
lbs. (kg)
cu.ft. (m
: Room temperature 80 F DB / 67 F WB, Ambient temperature 95 F DB / 75 F WB
: Room temperature 70 F DB / 60 F WB, Ambient temperature 47 F DB / 43 F WB
230 - 208 V / 1 Phase / 60 Hz
Cooling
33,000
32,000
10.6
10.6
830 / 710 / 590
10.3
10.5
230
208
A
14.9
15.5
W
3,290
3,120
A
Microprocessor
3 and Automatic control / 3 (Auto)
RCS-SH80UG (72-hour ON / OFF)
RCS-BH80UA. WL (72-hour ON / OFF)
Manual / Automatic
Washable, easy access
Electronic Expansion Control Valve
Outdoor unit is higher than indoor unit: 165 (50)
Outdoor unit is lower than indoor unit: 100 (30)
3 / 4 (19.05)
Indoor unit
14-9/16
(370)
59-1/16
(1,500)
9-7/16
(240)
18-3/16
(462)
62-9/16
(1,589)
11-5/8
(295)
73
(33)
90
(41)
3
)
7.7
(0.217)
DATA SUBJECT TO CHANGE WITHOUT NOTICE
I - 11
1. Specifications
KH3642
CH3642
Heating
40,000
39,000
25,000
24,000
(7.6)
(7.6)
230
208
187 - 253
17.8
19.1
3,860
3,810
3,000
2,900
40
Built-in 0 F
48 / 44 / 40
56
165 (50)
100 (30)
3 / 8 (9.52)
Outdoor unit
48-5/8
(1,235)
37-1/32
(940)
13-3/8
(340)
52-7/32
(1,326)
40
(1,016)
16-3/8
(416)
203
(92)
227
(103)
19.8
(0.56)
1
2
3
4
5
SM830082