Specifications - Honeywell C7195A Product Handbook

Water flow sensor
Table of Contents

Advertisement

SPECIFICATIONS

Model
C7195A water flow sensor
Ambient temperature
--20 ... + 85 _C
Dimensions
See fig. 11.
Fluid
Water for sanitary use
Permissible fluid temperatur
0 ... 80 _C
Minimum operating flow rate
1.5 liter/minute or lower
Maximum operating flow rate
30 liter/minute
Mounting position
 The shaft of the rotor shall be horizontal ¦ 5_. See fig. 5.
 Provided the shaft of the rotor is horizontal, most
positions are acceptable, but the position as indicated in
fig. 6. is not recommended because water will remain in
the sensor when the installation is drained (frost risk).
Shaft axis
5_
5_
Fig. 5. Mounting positions
All positions
Shaft axis
Fig. 6. Not recommended mounting position
Measuring range
2.1 ... 30 liter/min
Nominal output frequency
f = Q x 7.0 (Q = flow rate in l/min; f = pulse signal in Hz) with
> 60 mm straight pipe on both sides.
Accuracy
¦ 10% of measurement over the measuring range.
Withstand pressure
When a water pressure of 17.5 bar is applied, no external
leakage shall be measured and no body damage shall occur.
Water connections
1
PF
/
" minimum 8 mm (4.4 threads)
2
Recommended tightening torque of inlet/outlet connections
2.5 ... 3.5 Nm
Pressure drop
0.15 bar or less at 10 l/min flow rate.
(Outlet pressure is at atmospheric pressure)
Endurance
Indicated value will shift < 5% under following conditions:
10000 hr at 10 l/min and 20 _C
7000 hr at 4 l/min and 45 _C
or
100,000 cycles ON/OFF at 10 l/min and 45 _C
5_
5_
4
EN2R- -9029 0101R2- -NE

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents