2. SELECTING THE INSTALLATION SITE

2-1. Indoor Unit

AVOID:
● areas where leakage of flammable gas may be expected.
● places where large amounts of oil mist exist.
● direct sunlight.
● locations near heat sources which may affect the
performance of the unit.
● locations where external air may enter the room directly.
This may cause "sweating" on the air discharge ports,
causing them to spray or drip.
● locations where the remote controller will be splashed with
water or affected by dampness or humidity.
● installing the remote controller behind curtains or furniture.
● locations where high-frequency emissions are generated.
DO:
● select an appropriate position from which every corner of
the room can be uniformly cooled.
● select a location where the ceiling is strong enough to
support the weight of the unit.
● select a location where tubing and drain pipe have the
shortest run to the outdoor unit.
● allow room for operation and maintenance as well as
unrestricted air flow around the unit.
● install the unit within the maximum elevation difference
above or below the outdoor unit and within a total tubing
length (L) from the outdoor unit as detailed in Table 1-9.
● allow room for mounting the remote controller about 3 ft.
off the floor, in an area that is not in direct sunlight nor in
the flow of cool air from the indoor unit.
NOTE
Air delivery will be degraded if the distance from the floor to
the ceiling is greater than 10 ft.
W-3WAY_ECO-i_US.indd 23
W-3WAY_ECO-i_US.indd 23
Ceiling-Mounted T ype
Ceiling
Min. 10 in.
Front view
NOTE
The rear of the indoor unit can be installed flush
against the wall.
Air
discharge
Min. 2 ft.
Side vie w
Concealed Duct (High-Static Pressure) Type
4-Way Air Discharge Semi-Concealed Type
3 ft.
3 ft.
Fig. 2-2
1-Way Air Discharge Semi-Concealed Type
Obstacle
Air
discharge
Min. 2 in.
Fig. 2-3
Wall-Mounted T ype
Min.
6 in.
Front View
23
Wall
Min. 10 in.
Air intake
Max. 10 in.
Obstacle
Fig. 2-1
3 ft.
3 ft.
3 ft.
Ceiling
Min. 2 in.
Wall
Air
Wall
intake
Side view
Min.6 in.
Min.
6 in.
Fig. 2-4
2008/02/07 10:55:42
2008/02/07 10:55:42