1-6. Tubing Size
Table 1-10 Main Tubing Size (LA)
BTU/h
95.500
Total system
horsepower
Combined
outdoor units
Suction tubing
(ø22.22)
Discharge tubing
(ø19.05)
Liquid tubing
(ø9.52)
*1: If future extension is planned, select the tubing diameter based on the total horsepower after extension.
However extension is not possible if the resulting tubing size is two ranks higher.
*2: The balance tube (outdoor unit tube) diameter is ø3/8" (ø9.52).
*3: Type 1 tubing should be used for the refrigerant tubes.
*4: If the length of the longest tube (L1) exceeds 295 ft. (equivalent length), increase the main tube (LM) size by 1 rank for the
suction, discharge, and liquid tubes. (Use field-supply reducers.) (Select from Table 1-10 and Table 1-15.)
*5: If the longest main tube length (LM) exceeds 164 ft., increase the main tube size at the portion before 164 ft. by 1 rank for
the suction tubes and discharge tubes.
(For the portion that exceeds 164 ft., set based on the main tube sizes (LA) listed in the table above.)
Table 1-11 Main Tubing Size After Distribution (LB, LC...)
Below BTU/h
Total capacity
after distribution
Over BTU/h
Suction tubing
Tubing size
Discharge tubing
Liquid tubing
Below BTU/h
Total capacity
after distribution
Over BTU/h
Suction tubing
Tubing size
Discharge tubing
Liquid tubing
Table 1-12 Outdoor Unit Tubing Connection Size (
BTU/h
95.500
ø7/8"(ø22.22)
Suction tubing
ø3/4"(ø19.05)
Discharge
tubing
ø3/8"(ø9.52)
Liquid tubing
Balance tubing
W-3WAY_ECO-i_US.indd 12
W-3WAY_ECO-i_US.indd 12
Unit: in. (mm)
153.600
191.000
249.100
10
16
26
20
10
16
10
16
10
10
ø7/8"
ø1-1/8"
ø1-3/8"
(ø28.58)
(ø34.92)
ø3/4"
ø7/8"
ø1-1/8"
(ø22.22)
(ø28.58)
ø3/8"
ø1/2"
ø5/8"
ø3/4"
(ø12.70)
(ø15.88)
(ø19.05)
24.200
54.600
85.300
(2.5 hp)
(6 hp)
(9 hp)
24.200
54.600
(2.5 hp)
(6 hp)
ø5/8"
ø3/4"
ø3/4"
(ø15.88)
(ø19.05)
(ø19.05)
ø1/2"
ø5/8"
ø5/8"
(ø12.70)
(ø15.88)
(ø15.88)
ø3/8"
ø3/8"
ø3/8"
(ø9.52)
(ø9.52)
(ø9.52)
258.000
334.400
(27 hp)
(35 hp)
238.900
258.000
334.400
(25 hp)
(27 hp)
(35 hp)
ø1-3/8"
ø1-3/8"
ø1-1/2"
(ø34.93)
(ø34.93)
(ø38.10)
ø1-1/8"
ø1-1/8"
ø1-1/8"
(ø28.58)
(ø28.58)
(ø28.58)
ø3/4"
ø3/4"
ø3/4"
(ø19.05)
(ø19.05)
(ø19.05)
153.600
ø1-1/8"(ø28.58)
Brazing connection
ø7/8"(ø22.22)
Brazing connection
ø1/2"(ø12.7)
Brazing connection
ø3/8"(ø9.52)
Flare connection
307.100
32
16
16
102.400
124.200
143.300
(11 hp)
(13 hp)
(15 hp)
85.300
102.400
124.200
(9 hp)
(11 hp)
(13 hp)
ø7/8"
ø1-1/8"
ø1-1/8"
(ø22.22)
(ø28.58)
(ø28.58)
ø3/4"
ø3/4"
ø7/8"
(ø19.05)
(ø19.05)
(ø22.22)
ø3/8"
ø1/2"
ø1/2"
(ø9.52)
(ø12.70)
(ø12.70)
*1: If the total capacity of the indoor units con-
nected to the tube ends is different from the
total capacity of the outdoor units, then the
main tube size is selected based on the total
capacity of the outdoor units.
(For LA, LB, and LF in particular)
)
A
D
Unit: in. (mm)
12
Unit: in. (mm)
hp = horsepower
162.400
200.600
238.900
(17 hp)
(21 hp)
(25 hp)
200.600
143.300
162.400
(15 hp)
(17 hp)
(21 hp)
ø1-1/8"
ø1-1/8"
ø1-1/8"
(ø28.58)
(ø28.58)
(ø28.58)
ø7/8"
ø7/8"
ø1-1/8"
(ø22.22)
(ø22.22)
(ø28.58)
ø1/2"
ø5/8"
ø5/8"
(ø12.70)
(ø15.88)
(ø15.88)