Download Print this page

Mitsubishi Electric FX3U-232ADP User Manual page 6

Fx3g series
Hide thumbs Also See for FX3U-232ADP:

Advertisement

Item
Specification
Input response time
Approx. 10ms
• Sink input:
No-voltage contact
input
NPN open
collector transistor
Input signal form
• Source input:
No-voltage contact
input
PNP open
collector transistor
Photocoupler
Input circuit insulation
insulation
LED on panel lights
Input operation display
when photocoupler is
driven.
*1 Each value inside ( ) indicates the number of occupied points.
3.4.2
Examples of input wiring [AC power type]
1. Sink input type
2. Source input type
[1]
[1]
Fuse
Fuse
L
L
*
*
N
N
100 to 240V AC
100 to 240V AC
S/S
S/S
0V
0V
24V
24V
X000
X000
X001
X001
3-wire type
3-wire type
X002
X002
sensor
sensor
X003
X003
[2]
[2]
S/S
S/S
X000
X000
*Class D grounding
See section 3.3 for details.
[1]:Main unit, Input/output extension unit
(Common to both sink and source inputs)
[2]:Input/output extension block
(Common to both sink and source inputs)
3.4.3
Examples of input wiring [DC power type]
1.Sink input type
2.Source input type
[1]
[1]
Fuse
*1
*1
24V DC
S/S
S/S
*2
*2
X000
X000
X001
X001
3-wire type
3-wire type
X002
X002
sensor
sensor
X003
X003
[2]
[2]
S/S
S/S
X000
X000
*1 Class D grounding
See section 3.3 for details.
*2
Do not connect the [ ] terminals with others,
since they are not available.
[1]:Main unit, Input/output extension unit
(Common to both sink and source inputs)
[2]:Input/output extension block
(Common to both sink and source inputs)
3.4.4
Instructions for connecting input devices
As for the details of Instructions for connecting input devices, refer to
the following manual.
→ Refer to FX
Series User's Manual - Hardware Edition.
3G
1) In the case of no-voltage contact:
Fuse
The input current of this PLC is 5 to 7mA/24V DC.
Use input devices applicable to this minute current.
If no-voltage contacts (switches) for large current are used,
contact failure may occur.
24V DC
2) In the case of input device with built-in series diode:
The voltage drop of the series diode should be approx. 4V or
less.
When lead switches with a series LED are used, up to two
switches can be connected in series.
Also make sure that the input current is over the input-sensing
level while the switches are ON.
3) In the case of input device with built-in parallel resistance:
Use a device with a parallel resistance of 15kΩ or more.
When the resistance is less than 15kΩ, connect a bleeder
resistance.
4) In the case of 2-wire proximity switch:
Use a two-wire proximity switch whose leakage current is 1.5mA
or less when the switch is off.
When the current is 1.5mA or more, connect a bleeder
resistance.
3.4.5
Input specifications (100V AC input type)
Item
Number
FX
-8EX-UA1/UL
8 points
2N
of input
FX
-48ER-UA1/UL 24 points
points
2N
Input connecting type
Refer to FX
User's Manual - Hardware Edition
Input form
Input signal voltage
100V AC to 120V
Approx. 21kΩ/50Hz
Input impedance
Approx. 18kΩ/60Hz
4.7mA/100V AC 50Hz
Input signal current
6.2mA/110V AC 60Hz
ON input sensitivity
3.8mA/80V AC
current
OFF input sensitivity
1.7mA/30V AC
current
Input response time
Approx. 25ms to 30ms
Input signal form
Contact input
Input circuit insulation
Photocoupler insulation
LED on panel lights when
Input operation display
photocoupler is driven.
3.4.6
Examples of 100V AC input wiring
Input/
L
output
extension
unit
N
COM
X000
X001
X002
Input/
output
COM
extension
X000
block
X001
*Do not take input signals from loads generating surge.
3.5
Relay output specifications and example of
external wiring
As for the details of the relay output specifications and external
wiring, refer to the following manual.
→ Refer to FX
3G
3.5.1
Relay output specifications
Specification
Item
FX
2N
-8ER
FX
3G
-14MR
Series
3G
FX
2N
-8EYR
Number
FX
-24MR
3G
of output
points
FX
-40MR ,
3G
FX
-32ER ,
2N
FX
-16EYR
2N
FX
-60MR ,
3G
FX
2N
-48ER
Output connecting type
Output form
External power supply
Resistance load
Max. load
Inductive load
Min. load
Open circuit leakage current
OFF
ON
Response
time
ON
OFF
Circuit insulation
Display of output operation
*1 Each value inside ( ) indicates the number of occupied points.
*2 Between 250V and 240V CE, UL, and cUL are not compliant.
Fuse
*
MC *
Series User's Manual - Hardware Edition.
Specification
1
4 points (8 points)*
1
6 points (8 points)*
8 points
1
10 points (16 points)*
16 points
24 points
Refer to FX
3G
Series User's
Manual - Hardware Edition
Relay
30V DC or less
*2
240V AC or less
*3
2A/point
80VA
5V DC, 2mA (reference value)
-
Approx. 10ms
Mechanical insulation
LED lights when power is applied
to relay coil.

Advertisement

loading

This manual is also suitable for:

Fx3u-4ad-adpFx3u-485adpFx3u-4da-adpX3u-4ad-pt-adpFx3u-4ad-tc-adpFx3u-485adp-mb ... Show all