3.1
Wiring
This section explains the wiring of the terminal type.
For the connectors types, refer to the following manual.
→ Refer to FX
Series User's Manual - Hardware Edition.
3G
3.1.1
Cable end treatment and tightening torque
For the terminals of FX
3G
series PLC, M3 screws are used.
The electric wire ends should be treated as shown below.
Tighten the screws to a torque of 0.5 to 0.8 N
m.
Do not tighten terminal screws with a torque exceeding the
regulation torque.
Failure to do so may cause equipment failures or malfunctions.
• When one wire is connected to one terminal
φ3.2 (0.13")
Terminal
Solderless
screw
terminal
6.2 mm (0.24")
or less
φ3.2 (0.13")
6.2 mm (0.24")
Terminal
or less
<Reference>
Terminal
Pressure
Type No.
Certification
Manufacturer
Bonding Tool
JAPAN
FV1.25-B3A
SOLDERLESS
UL Listed
YA-1(JST)
TERMINAL MFG
FV2-MS3
CO LTD (JST)
• When two wires are connected to one terminal
φ3.2 (0.13")
Terminal
Solderless
6.2 mm (0.24")
screw
terminal
or less
6.3 mm(0.25")
or more
φ3.2 (0.13")
6.2 mm (0.24")
Terminal
or less
6.3 mm(0.25")
or more
<Reference>
Terminal
Pressure
Type No.
Certification
Manufacturer
Bonding Tool
JAPAN
SOLDERLESS
FV1.25-B3A UL Listed
YA-1(JST)
TERMINAL MFG
CO LTD (JST)
3.1.2
Removal and installation of quick-release terminal
block
Removal
Unscrew the terminal block mounting screw [both right
and left screws] evenly, and remove the terminal block.
Installation Place the terminal block in the specified position, and
tighten the terminal block mounting screw evenly [both
right and left screws].
Tightening torque 0.4 to 0.5 N
m
Do not tighten the terminal block mounting screws with
a torque exceeding the regulation torque.
Failure to do so may cause equipment failures or
malfunctions.
* Pay attention so that the center of the terminal block
is not lifted.
3.2
Power supply specifications and example of
external wiring
As for the details of the power supply specifications and example of
external wiring, refer to the following manual.
→ Refer to FX
Series User's Manual - Hardware Edition.
3G
3.2.1
Power supply specifications
[Main unit, Input/output extension units]
Specification
Item
AC power type
DC power type
Supply voltage
100 to 240V AC
24V DC
Allowable supply voltage
85 to 264V AC
20.4 to 28.8V DC
range
Rated frequency
50/60Hz
Operation can
Operation can be
be continued
continued upon
Allowable instantaneous
upon occurrence
occurrence of
power failure time
of instantaneous
instantaneous
power failure for
power failure for
10 ms or less.
5 ms or less.
FX
-14M ,
3G
250V 1A
125V 2.5A
FX
-24M
3G
FX
-40M ,
3G
250V 3.15A
125V 3.15A
Power fuse
FX
-60M
3G
FX
-32E
250V 3.15A
2N
FX
-48E
250V 5A
250V 5A
2N
30A max. 5ms or
less/100 V AC
30A max. 1ms or
Main unit
50A max. 5ms or
less/24 V DC
less/200 V AC
Rush current
40A max. 5ms or
FX
-32E ,
less/100 V AC
2N
FX
-48E
60A max. 5ms or
2N
less/200 V AC
FX
3G
-14M
31W
19W
FX
-24M
32W
21W
3G
FX
-40M
37W
25W
3G
Power
consumption
*1
FX
-60M
40W
29W
3G
FX
-32E
30W(35VA)
2N
FX
-48E
35W(45VA)
30W
2N
Main unit
400mA
24V DC
service
FX
2N
-32E
250mA
power supply
FX
-48E
460mA
2N
5V DC built-
FX
-32E
2N
in power
690mA or less
690mA or less
FX
-48E
2N
supply
*1 This item shows values when all 24V DC service power
supplies are used in the maximum configuration connectable to
the main unit or input/output extension units,
For the power (current) consumed by the input/output
extension units/blocks, refer to FX
Series User's Manual -
3G
Hardware Edition. (The DC power type main unit does not have
a 24V DC service power supply.)
→ For the power consumed by the special extension blocks,
refer to the respective manual.
→ Refer to FX
Series User's Manual - Hardware Edition.
3G
3.2.2
Example of external wiring (AC power type)
100 to 240V AC power is supplied to the main unit and input/output
extension unit.
→ For the details of wiring work, refer to section 3.1.
PLC
Main unit
L
*
N
Input/output
-
extension
Fuse
unit
L
N
MC
-
*Class D grounding
See section 3.3 for
Power supply for loads connected
details.
to PLC output terminals
3.2.3
Example of external wiring (DC powewr type)
-
24V DC power is supplied to the main unit and input/output
extension unit.
→ For the details of wiring work, refer to section 3.1.
PLC
Main unit
-
*
-
-
Input/output
-
extension
Fuse
unit
MC
* Class D grounding
See section 3.3 for
Power supply for loads connected
details.
to PLC output terminals
3.3
Grounding
Ground the PLC as stated below.
• Perform class D grounding. (Grounding resistance: 100 Ω or less)
• Ground the PLC independently if possible.
If it cannot be grounded independently, ground it jointly as shown
100 to 240V AC
below.
Other
PLC
equipment
Breaker
Power on
Independent grounding
Emer-
(Best condition)
gency
PL
• Use ground wires thicker than AWG14 (2 mm
MC
• Position the grounding point as close to the PLC as possible to
MC
decrease the length of the ground wire.
3.4
Input specifications and external wiring
As for the details of the Input specifications and external wiring, refer
to the following manual.
MC
→ Refer to FX
3.4.1
Input specifications (24V DC input type)
DC
power
FX
-8ER
2N
supply
FX
-14M ,
3G
FX
-8EX
2N
DC
AC
FX
-24M
3G
Number of
input
FX
-16EX ,
2N
points
FX
2N
-32E
FX
-40M ,
3G
FX
-48E
2N
FX
-60M
3G
Input connecting type
24V DC
Input form
Circuit protector
Main unit
Input
Power on
signal
Input/output
Emer-
voltage
extension
gency
PL
unit
MC
MC
Main unit
Input
impedance
Input/output
extension unit/block
MC
Main unit
Input
signal
current
Input/output
extension unit/block
Main unit
ON input
sensitivity
current
Input/output
extension unit/block
OFF input sensitivity current
Other
Other
PLC
PLC
equipment
equipment
Shared grounding
Common grounding
(Good condition)
(Not allowed)
2
).
Series User's Manual - Hardware Edition.
3G
Item
Specification
1
4 points (8 points)*
8 points
1
14 points(16 points)*
16 points
24 points
1
36 points(40 points)*
Refer to FX
Series
3G
User's Manual -
Hardware Edition
AC power type 24V DC +10%, -10%
DC power type 20.4 to 28.8V DC
AC power type 24V DC +10%, -10%
DC power type 24V DC +20%, -30%
X000 to X007
3.3kΩ
X010 or more
4.3kΩ
4.3kΩ
X000 to X007
7mA/24V DC
X010 or more
5mA/24V DC
5mA/24V DC
X000 to X007
4.5mA or more
X010 or more
3.5mA or more
3.5mA/24V DC
1.5mA or less