Introduction
The Intelligent Thermostat has a space
temperature sensor, five user push buttons,
and a 2 line x 8 character dot matrix LCD
to show room temperature, time, outside air
temperature, setpoint, and other optional
parameters (depending upon the operation).
72 ° F
RoomTemp
ROOM/
OUTSIDE
*
OVERRIDE
Figure 1 - NXT-INT-01 Intelligent Thermostat
Installation
The thermostat connects to the controllers
via a 2-wire (#22 AWG, single twisted pair)
cable. The NexSys thermostat communica-
tions bus carries power and communica-
tions for the Intelligent thermostat.
Wiring
WARNING - TO PREVENT ELECTRI-
CAL SHOCK OR DAMAGE TO THE
EQUIPMENT, YOU MUST DISCON-
NECT THE POWER SUPPLY TO THE
ELECTRONIC CONTROLLER
BEFORE YOU MAKE THE WIRING
CONNECTIONS.
All wiring is low voltage and should be in
accordance with local regulations and the
National Electrical Code.
Use shielded cable only when it is required.
Most applications do not require shielding
and will benefit from unshielded cable.
When using the optional shielded cable,
ground only one end of the shield. Low
voltage control wiring should not be run in
the same conduit as line voltage wiring or
other conductors that supply highly-
inductive loads (such as contactors, coils,
motors, generators, etc.).

INSTALLATION GUIDE

CAUTION - MAKE ALL CONNEC-
TIONS AND CHECK ALL CONNEC-
TIONS BEFORE APPLYING
POWER. IMPROPER WIRING MAY
CAUSE PERMANENT DAMAGE TO
THIS EQUIPMENT.
Wiring Recommendations
Unshielded
Stranded, 22AWG: Belden #8442(2-
wire), Belden #8444(4-wire)
Plenum-rated, Stranded, 22AWG: Belden
#82442(2-wire), 82444(4-wire)
Stranded, 18AWG: Belden #8461(2-
wire), Belden #8489(4-wire)
Plenum-rated, Stranded, 18AWG: Belden
#87740(2-wire), 82489(4-wire)
Shielded
Stranded: Belden #8761
Solid: Belden #8450
Plenum-rated, Stranded: Belden
#88761other equipment.
To Wire the Intelligent Thermotat:
1. Connect the Red wire of the stat's pigtail
to the STAT + terminal of the controller.
2. Connect the Black wire of the stat's
pigtail to the controller's STAT - terminal.
Refer to Figure 2 below.
Figure 2 - Wiring connection for the Intelligent Thermostat
www.johnsoncontrols.com
Mounting
Mount the thermostat where it is exposed
to normal air circulation and where it senses
the average temperature of the space being
controlled (normally about 5 feet above the
floor). Do not mount it where it could be
affected by heat or cold from windows,
pipes, doors, lamps, sunlight, outside walls,
or other sources. See Figure 3 for dimen-
sions.
Figure 3 - Intelligent Thermostat dimensions
BLACK
RED
72 ° F
RoomTemp
ROOM/
OUTSIDE
*
OVERRIDE
LIT-TD-2006 11/2002
Literature Part # 24-9869-5 Rev. A

Advertisement

loading

Summary of Contents for Johnson Controls NXT-INT-01

  • Page 1: Installation Guide

    NXT-INT-01 Intelligent Thermostat INSTALLATION GUIDE Installing and Operating the NXT-INT-01 Intelligent Thermostat Mounting Introduction CAUTION - MAKE ALL CONNEC- Mount the thermostat where it is exposed TIONS AND CHECK ALL CONNEC- The Intelligent Thermostat has a space to normal air circulation and where it senses...
  • Page 2 Standby mode for one minute periods. Repairs and Replacement Do not make field repairs. Please contact Johnson Controls at (800) 765- 7773 for replacement and other services. Johnson Controls, Inc. reserves the right to update specifications when appropriate. Information contained in...