External Input & Output; External Input - Fujitsu ASTG12LVCC Design & Technical Manual

Air conditioner wall mounted type refrigerant r410a inverter, indoor/outdoor
Table of Contents

Advertisement

11.
EXTERNAL INPUT & OUTPUT
Connector
CNA01
CNB01
CNB02
11-1.

EXTERNAL INPUT

CONTROL INPUT (Operation/Stop or Forced stop)
The air conditioner can be remotely operated by means of the following on-site work.
"Operation/Stop" mode or "Forced stop" mode can be selected with function setting of indoor unit.
Unit operation is started at the following contents by adding the contact input of a commercial ON/OFF switch to a
connector on the external control PC board and turning it ON.
Unit operation
Operation mode
Set temperature
Air flow mode
Up-down air direction (swing)
Left-right air direction (swing)
Circuit diagram example
indoor unit
control PC board
Communication kit
Optional parts
* Make the distance from the PC board to the connected unit within 10m.
Contact capacity : 24VDC or more, 10mA or more.
Please use the non-polar relays and switches.
When function setting is "Operation/Stop" mode
ON
Input signal
OFF
Operation
Indoor unit
Stop
When function setting is "Forced stop" mode
ON
Input signal
OFF
Forced stop
Command
Normal
Operation
Indoor unit
Stop
Remote controller
Parts (Optional)
Parts name
External connect kit
Communication kit
* For operating the EXTERNAL function, the Compact wall mounted type requires the communication kit in addition to
the wire (UTY-XWZXZ5).
Wire (External input) : UTY-XWZXZ5
INPUT
Control input
-
-
Initial starting after turned power on
Auto changeover
24°C
AUTO
Standard air direction (swing OFF)
Standard air direction (swing OFF)
Connected unit
Connector
Ex.) Switch
1
3
*10 m
Signal
Field supply
ON
Model name
UTY-XWZXZ5
UTY-TWBXF
- (01 - 22) -
OUTPUT
-
Operation status output
Error status output
Temperature at previous operation
Air direction at previous operation
Air direction at previous operation
ON
ON
Remote control
operation invalidity
REMARKS
See external
input/output settings for
details.
Other than initial starting
Mode at previous operation
Mode at previous operation