Burner Setup - Biasi B40/6 Manual And Installation Instructions

Table of Contents

Advertisement

PAGE 10
The following information applies only to the BIASI B-40 series boilers at a maximum output
for power venters or lined chimneys only.
BURNER MANUFACTURER
Boiler Model
Burner Model
Firing Rate
Insertion Depth
Nozzle
Spray Pattern
Pump Pressure
Head Position
Air Setting
BURNER MANUFACTURER
Boiler Model
Burner Model
Firing Rate
Insertion Depth
Nozzle
Spray Pattern
Pump Pressure
Turbulator
Air Gate
BURNER MANUFACTURER
Boiler Model
Burner Model
Firing Rate
Insertion Depth
Nozzle
Spray Pattern
Pump Pressure
Head Type
Head Position
Air Setting
Good, reliable operation with a minimum of service starts with attention to the small details:
1. Setting the nozzle position and electrodes "by the book" using the manufacturer's gauges.
2. Installing a quality micron filter at the burner.
3. Making careful/tight flare connections without couplings on oil suction line.
4. Checking fuel pump pressure.
5. Checking draft at the breeching to insure it is adequate to overcome flue gas resistance.
6. Setting the air band properly with well maintained instruments. A good target is 11% to 12.5% of (CO
to 3.8% of (O
).
2
Note: Oil and Gas burners on B40-series boilers cannot be properly commissioned
All manuals and user guides at all-guides.com

8. Burner Setup:

B-406
B-407
P2-KA
P2-K
2.2 GPH
2.8 GPH
3.5 GPH
FULL
FULL
2.00 X 45
2.25 X 60
2.75 X 60
solid
solid
140 psi
170 psi
12
16
11.50
15.00
Riello
B-406
B-407
F-10
F-10
2.4 GPH
2.6 GPH
3.3 GPH
4.5"
4.5"
2.00X60
2.00X60
B
B
145 PSI
175 PSI
3.75
4.5
5
6
Beckett
B-407
B-407
CF 375
CF 375
2.1 GPH
2.7 GPH
3.2 GPH
4.5"
4.5"
1.75X60
2.00X45
ES
hollow
140 psi
180 psi
0
2
9/0
3/1
Heatwise
B-408
B-409
B-410
P2-K
DE-10
DE-10
4.25 GPH 5.0 GPH
FULL
FULL
FULL
3.25 X 60 3.75 X 60
solid
solid
175 psi
175 psi
175 psi
18
1
18.00
3.5
B-408
B-409
B-410
F-15
F-15
4.0 GPH
4.6 GPH
4.5"
4.5"
2.50X60
3.00X60
3.50X60
B
B
175 PSI
175 PSI
175 PSI
1.8
2.1
3
4
B-408
B-409
B-410
CF 500
CF 500
CF 800
3.7 GPH
4.3 GPH
4.5"
4.5"
2.75X45
2.75X45
3.25X45
solid
solid
140 psi
180 psi
175 psi
3
4.5
7/0
10/0
BIASI B/40
B-411
B-412
DE-10
DE-10
5.7 GPH
6.4 GPH
FULL
FULL
4.5 X 45
5.50 X 45
solid
solid
solid
160 psi
140 psi
1.5
2
2.5
4.5
5.5
6.75
B-411
B-412
F-15
F-20
F-20
5.3 GPH
5.9 GPH
4.5"
4.5"
4.5"
4.0X60
4.5X60
B
B
B
175 PSI
175 PSI
2.8
3.1
5
5.5
4
6
B-411
B-412
CF 800
CF 800
4.8 GPH
5.3 GPH
4.5"
4.5"
4.5"
4.0X30
4.0X30
solid
solid
solid
145 psi
180 psi
3
3
4.5
7/0
8/0
10/2
without instruments and gauges.