Operation - Siemens PMI-2 Installation Instructions Manual

Person-machine interface

Advertisement

Figure 5
Connecting the PMI-2 to the CC-5

OPERATION

Siemens Industry, Inc.
Building Technologies Division
Make sure that all cables snap fully into their connectors and close the locking levers
over the top of each cable connector. Secure the cable in the back box using cable
ties and the tie down points in the enclosure. The cable must have sufficient slack to
allow the inner door to open fully without putting stress on the cable.
In the normal standby condition the PMI-2 displays the site specific custom message,
the time and date, and a synopsis of the system status.
When an event occurs in the system, the display enters the Alert mode. The event is
displayed, the local audible sounds and the appropriate LED blinks. If the event
caused notification appliances to sound the Audibles On indicator lights. At the
bottom of the screen an acknowledge button is displayed. Pressing this button
acknowledges the event and silences the local audible. Once all events are acknowl-
edged a reset button becomes available in the lower right side of the display. If
notification appliances were active, two additional buttons appear at the bottom of
the screen. These allow the operator to silence or unsilence the notification appli-
ances. When the notification appliances are silenced the Audibles Silenced LED
lights. The system can only be reset with the notification appliances silenced.
If more events are present in the system than can be displayed on a single screen a
scroll bar appears to the right of the event list. Pressing the up and down navigation
buttons to the right of the LCD allows the operator to move through the list. The
selected event is highlighted in the display. Pressing the More Info button will display
a screen showing details relating to the selected event. Other buttons also appear at
the bottom of this screen. There is an expanded text message available and a
selection to show all of the devices associated with the event that are active. The
operator can return to the previous screen by pressing the ESC button. (For more
detail on PMI-2 operation, refer to the FireFinder-XLS Manual, P/N 315-033744.)
Figure 6
Connecting the PMI-2 to the RNI
4