Pressure Switches - International comfort products R9MSB0601716A Service And Technical Support Manual

R9msb series; single stage, psc blower motor 35" tall, high efficiency condensing gas furnace
Table of Contents

Advertisement

Electrical Controls and Wiring

Pressure Switches

Each pressure switch is labeled with the reference location
(noted as "COLLECTOR BOX−LPS" or "HOUSING−HPS"
ON THE SWITCH). The nominal break point of each switch
is shown on the label below the reference location in inches
of water column, "W.C." The maximum and minimum break
point of the switch is +/− 0.05 inches of water column from
the nominal break point of the switch. The maximum make
point of the switch is 0.10 inches of water above the
maximum break point of the switch
Example: Nominal break point on pressure switch is
0.68−in. W.C. The minimum break point of the switch is
0.63−in. W.C. The maximum break point of the switch is
0.73−in. W.C. The maximum make point of the switch is
0.83−in. W.C.
WARNING
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
There may be more than one electrical supply to the
furnace. Check accessories and cooling unit for
additional electrical supplies that must be shut off
during furnace servicing. Lock out and tag switch with
a suitable warning label.
The electrical ground and polarity for 115−v wiring must be
properly maintained. Refer to Figure 7 for field wiring
information and to Figure 16 for furnace wiring information.
NOTE: If the polarity is not correct, the STATUS LED on the
control will flash rapidly and prevent the furnace from
heating. The control system also requires an earth ground
for proper operation of the control and flame−sensing
electrode.
The 24−v circuit contains an automotive−type, 3−amp. fuse
located on the control. (See Figure 2.) Any shorts of the
24−v wiring during installation, service, or maintenance will
cause this fuse to blow. If fuse replacement is required, use
ONLY a 3−amp. fuse. The control LED will display status
code 24 when fuse needs to be replaced.
THE BLOWER IS LOCATED
TO THE RIGHT OF THE
BURNER SECTION, AND
AIR CONDITIONED AIR IS
DISCHARGED TO THE LEFT.
THE BLOWER IS
LOCATED ABOVE THE
BURNER SECTION, AND
CONDITIONED AIR IS
DISCHARGED DOWNWARD
12
Troubleshooting
Refer to the service label. (See Figure 5—Service Label.)
The Troubleshooting Guide (See Figure 15) can be a useful
tool in isolating furnace operation problems. Beginning with
the word "Start," answer each question and follow the
appropriate arrow to the next item.
The Guide will help to identify the problem or failed
component. After replacing any component, verify correct
operation sequence.
Proper instrumentation is required to service electrical
controls. The control in this furnace is equipped with a
Status Code LED (Light−Emitting Diode) to aid in
installation, servicing, and troubleshooting. Status codes
can be viewed at the indicator in blower door. The amber
furnace control LED is either ON continuously, rapid
flashing, or a code composed of 2 digits. The first digit is the
number of short flashes, the second digit is the number of
long flashes.
For an explanation of status codes, refer to service label
located on control door or Figure 5, and the troubleshooting
guide which can be obtained from your distributor.
Retrieving Stored Fault Codes
NOTE:
signal (24-v on W, Y, G, etc.) is present, or if any delays
such as blower off-delays are active.
The stored status codes will NOT be erased from the control
memory when 115- or 24-v power is interrupted. See the
Service Label (Figure 5) for more information. The most
recent fault code may be retrieved as follows:
1. Leave 115-v power connected to furnace.
2. Observe the status LED through the blower door (the
3. Remove the Main/Control door (the upper door on
4. BRIEFLY (2−3 seconds) disconnect and reconnect
5. The LED will flash the last stored fault code. Refer to
6. A component test sequence will follow.
7. Reinstall the Main/Control door.
Figure 6 − Multipoise Orientations
Specifications subject to change without notice.
Fault codes cannot be retrieved if a thermostat
lower door on upflow applications) indicator. Refer to
the Service Label (Figure 5) to interpret the LED.
upflow installations).
ONE of the main limit wires.
the Service Label (Figure 5) to interpret the LED.
THE BLOWER IS
LOCATED BELOW THE
BURNER SECTION, AND
CONDITIONED AIR IS
DISCHARGED UPWARD.
LOCATED TO THE LEFT
OF THE BURNER SECTION,
AND CONDITIONED AIR IS
DISCHARGED TO THE RIGHT.
THE BLOWER IS
A02097
440 04 6000 00

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

R9msb0801716aR9msb1002122aR9msb1202422a

Table of Contents