Introduction - ABB REC 561 User Manual

Bay level control terminal
Table of Contents

Advertisement

ABB Network Partner AB
Version 1.0-00
October 1996
Function:

1 Introduction

Apparatus control
Basic
The apparatus control function is a program supervising operation of a set
of high-voltage apparatuses within a bay. Apparatuses in the form of
breakers, disconnectors, and earthing switches.
Fig. 1 gives an overview from what places the apparatus control function
receive commands. Orders to operate an apparatus can come from the CC
(Control Centre), the station MMI, or the local back-up panel (via the I/
O).
When operating from the local back-up panel, the apparatus control func-
tion can be bypassed. The back-up panel is hard wired to the apparatuses
for this purpose.
Station MMI
back-up panel
Fig. 1
Overview of the apparatus control functions
Features in the apparatus control function:
• Supervision of valid operator place (one operator place at a time)
• Each apparatus are prepared to be included in a sequence
• Each apparatus can be interlocked
• The breakers can be connected to synchro-check
• Reservation of bays
• Supervision of operating apparatus
CC
GW
REC 561
REC 561
Apparatus
Apparatus
Control
Control
I/O
I/O
1MRK 580 150-XEN
Page
6
- 1
LON
breakers,
disconnectors,
earthing switches
(X80150-1)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents