2.3
Dry Contacts
The UPS provides input dry contacts and output dry contacts.
2.3.1
Input Dry Contacts
There are several input dry contacts at the X3 slot.
Figure 8
Input dry contacts
Table 1
Input dry contacts at X3
Position
Name
J4.1
ENV
J4.2
BtG
J4.3
GEN
J4.4
+12V
1 - Must be configured by configuration software before becoming active.
2 - When activated, the charger current can be limited, via software, to a percentage of the full charger current (0-100%).
3 - Activating this feature turns the battery charger off.
2.3.2
Maintenance Bypass Cabinet Interface
J26 and J30 are the MBC interface.
Table 2
Maintenance bypass cabinet interface
Position
Name
J26.1
T_IT
J26.2
AUX_I
J26.3
+12V
J26.4
GND
J30.1
FUSE
J30.2
F_FAN
J30.3
T_OT
J30.4
AUX_O
1 - Must be configured by software before becoming active
NOTE
All auxiliary cables of terminal must be double insulated. Wire should be 16-20AWG stranded.
Description
3
Battery Room Alarm (N.C.)
Battery Ground Fault Detection (N.C.)
1,2
Generator Join Detection (N.O.)
+12V Power
Description
1
Input transformer over temperature (N.C.)
Reserved
+12V Power
Power Ground
Reserved
Fan Fail Alarm (N.C.)
1
Output Transformer Overtemperature (N.C.)
Reserved
15
Electrical Connections