Operating Guide ECL Comfort 210/296/310, application A217/A317
MENU > Settings > Flow / power limit
Input type
Choice of input type from flow / energy meter
See Appendix "Parameter ID overview"
OFF:
No input
IM1 -
Flow / energy meter signal based on pulses.
IM5:
EM1 -
Flow / energy meter signal from M-bus.
EM5:
MENU > Settings > Flow / power limit
Actual (actual flow or power)
The value is the actual flow or power based on the signal from flow / energy
meter.
MENU > Settings > Flow / power limit
Limit (limitation value)
This value is in some applications a calculated limitation value, based on the
actual outdoor temperature.
In other applications the value is a selectable limitation value.
See Appendix "Parameter ID overview"
MENU > Settings > Flow / power limit
Adapt. time (adaptation time)
Controls how fast the flow / power limitation adapts to the desired
limitation.
See Appendix "Parameter ID overview"
OFF:
The control function is not influenced by the 'Adapt.
time' .
Minor
The desired temperature is adapted quickly.
value:
Major
The desired temperature is adapted slowly.
value:
VI.LG.U3.02
1x109
The setting range for IM and EM depends on chosen subtype.
1x111
1x112
If the 'Adapt. time' is too low, there is a risk of unstable control.