Siemens ILP-1 Installation Instructions page 3

Advertisement

PROGRAMMING
Each detector on a loop must be programmed to
respond to a unique system address.
1. To program the detector address, use the
Model FPI-32 Programmer/Tester. Refer
to the FPI-32 OPERATIONS MANUAL, P/N 315-
090077.
2. Record the loop and device number (system
address) for the detector on the detector label and
on the base to prevent installing the detector in the
wrong base.
SENSITIVITY ADJUSTMENT
XL3 Systems
The sensitivity of each detector can be adjusted from
the System XL3 Control Panel. Refer to the SYSTEM
XL3 OPERATION, INSTALLATION AND MAIN-
TENANCE MANUAL, P/N 315-083206.
MXL Control Panel
The sensitivity of each detector can be adjusted from
the MXL/MXLV/MXL-IQ control panel. Refer to the MXL/
MXLV OPERATION, INSTALLATION, AND MAIN-
TENANCE MANUAL, P/N 315-092036, or the MXL-IQ
OPERATION, INSTALLATION, AND MAINTENANCE
MANUAL, P/N 315-093624, as applicable.
ICON-1 Modules (in IXL Systems)
The sensitivities of detectors on an ICON-1 module are
set from the IXL Control Panel. Refer to ICON-1
Instructions, P/N 315-093087, as well as the IXL
Programming Manual, P/N 315-092394, for additional
information.
TESTING AND SENSITIVITY MEASUREMENTS
XL3 Systems
Only qualified service personnel should test.Refer to
the SYSTEM XL3 OPERATION, INSTALLATION AND
MAINTENANCE MANUAL, P/N 315-083206. Test as
frequently as required by the Installation and Test
Guidelines of NFPA 72. Obtain detector sensitivity
measurements from the System XL3 Control Panel.
Refer to System XL3 Manual for further information.
The detector sensitivity indicated by the System XL3
Control Panel should fall within the range on the
detector nameplate label. If not, refer to the
DETECTOR CLEANING section.
MXL/MXL-IQ Control Panels
Only qualified service personnel should test. Refer to
the MXL/MXLV OPERATION, INSTALLATION, AND
MAINTENANCE MANUAL, P/N 315-092036, or the
MXL-IQ OPERATION, INSTALLATION, AND
MAINTENANCE MANUAL, P/N 315-093624, as
applicable. Test as frequently as required by the
Installation and Test Guidelines of NFPA 72. Obtain
detector sensitivity measurements from the MXL
Control Panel. Refer to the MXL/MXLV/MXL-IQ Manual
for further information. The detector sensitivity
indicated by the MXL Control Panel should fall within
the range on the detector nameplate label. If not, refer
to DETECTOR CLEANING below.
ICON-1 Modules (in IXL Systems)
Only qualified service personnel should test. Refer to
the IXL Manuals, P/Ns 315-092394 and 315-092371
as well as the ICON-1 Instructions P/N 315-093087
for information. Test as frequently as required by the
Installation and Test Guidelines of NFPA 72. Obtain
detector sensitivity measurements from the IXL Control
Panel. The detector sensitivity indicated by the IXL
Control Panel should fall within the range on the
detector nameplate label. If not, refer to the
DETECTOR CLEANING section.
If the XL3, MXL/MXLV/MXL-IQ, or IXL (ICON-1)
is connected to a Fire Department, etc., or activates
an external system (fire extinguishing, etc.),
disarm the appropriate outputs before servicing
to prevent activation. (Refer to the appropriate
Manual for the procedure.) Be sure to reset and
re-arm the system at completion of servicing.
Notify facility personnel that the system is being
serviced so that any alarm soundings can be
ignored during the period of service.
The ILP-1/ILPT-1 detectors can also be tested
using the FPI-32 Programmer/Tester. Refer to the
OPERATIONS MANUAL, P/N 315-090077.
DETECTOR CLEANING
Systems XL3 and MXL automatically indicate the
trouble message INPUT DEVICE REQUIRES
SERVICE for any detector whose smoke sensitivity
increases to the level where normally low levels of
3