Engine Break-In Requirements; Resetting Maintenance Alarms - Generac Power Systems MDG25IF4 Owner's Manual

Diesel generator
Hide thumbs Also See for MDG25IF4:
Table of Contents

Advertisement

Check engine oil level
Check engine coolant level
Check fuel level
Drain fuel filter
Check tire pressure
Check all electrical connections
Clean battery
Check fan belt tension (replace if necessary)
Inspect radiator fins for debris; clean as
required
Pre-heating condition check
Check engine starting and noise conditions
Check exhaust smoke condition
Perform
Daily Walk Around Inspection
Replace engine oil
Replace fuel filter elements
Clean water sedimenter element
Electromagnetic pump filter replacement or
cleaning
Oil filter element replacement
Replace air filter element
Lubricate leveling jacks
Checking Generator Drive Plate Torque
Replace fan belt
Service air cleaner filter elements
*
If the unit is operated in a harsh environment or fuel quality is questioned, replace every 250 hours instead of every 500 hours.

Engine Break-In Requirements

NOTE: During the first 20 hours of operation, avoid long
periods of no load or sustained maximum load operation.
If the generator is to run for longer than five minutes
without a load, shut down the generator.
Operate the engine at heavy loads (60–90% of
maximum) as much as possible. If the engine has spent
significant time at idle, constant speed(s), or light load, or
if makeup oil is required, a longer break in period may be
needed. Refer to the engine operator's manual for a full
description of necessary procedures on the addition of
break-in oil and extension of the break-in period. For
more information on regular maintenance intervals, refer
to
Basic Maintenance
Schedule.
Owner's Manual for MDG25IF4
Table 4-1. Basic Maintenance Schedule
Item
First 50
Hrs.
Every
Daily
(Break-
250
in
Hrs.
Period)
*

Resetting Maintenance Alarms

The PowerZone controller will display a warning
message when the unit is due for maintenance or
service. The maintenance or service interval is set at
250, 500 and 3,000 hours of engine running time. Once
the unit has been serviced, the appropriate maintenance
alarm reminder must be reset. Proceed as follows to
reset the maintenance alarms:
1. With the unit shut down, move the control power
switch to CONTROL ON (I). The controller will
toggle automatically to the home screen after
initialization.
2. Press ▲, ►, ▼, or ◄ to enter the maintenance
screens.
Maintenance
Every
Every
2000
Require
500 Hrs.
Hrs.
*
*
*
As
d
37