XPP-5 with IMA (internally mounted pre-amplifier)

WHT
BLK
GRN
XPP-5 cable must be run in dedicated, approved metal conduit, boxes and fittings and to
procedures in accordance with all governing regulations. See table below for lengths
from probe at MFA 4p.
Refer to Interconnection Diagram for the XPP-5 (drawing number 23650131) on
Note:
page 21
.
Cable length from RMA or IMA to MFA 4p
Wire
gauge
7ML19985FM01
Length in feet
22 AWG
2500
2
(0.34 mm
)
18 AWG
5000
2
(0.75 mm
)
12 AWG
25000
2
(4 mm
)
MFA 4p - INSTRUCTION MANUAL
7
8
9
Length in
metres
760
1520
7600
MFA 4p