set boiler status (Figure 11.10)
Figure 11 .10
25 Switch off the boiler and turn off the hot water tap(s).
26 Close the air-flue sampling points.
27 After adjustment fit the protective brass plug ("C" - Figure
11.2).
Important: after the gas pressure checks and any adjust-
ment operations, all of the test points must be sealed .

11 .4 Checks

Warning: isolate the boiler from the mains electrici-
ty supply before removing any covering or compo-
nent .
Check the on-off operators coils
1 Remove the front panel of the case.
2 Disconnect the electrical connector "E" (Figure 11.2).
3 Measure the electrical resistance between the connector pins
of the on-off operators as illustrated in Figure 11.11.
Upper on-off operator
approx. 6400 *
Lower on-off operator
approx. 920 *
*at ambient temperature.
Figure 11 .11

11 .5 Removal of the gas valve

Warning: isolate the boiler from the mains electrici-
ty supply before removing any covering or compo-
nent .
1 Remove the front panel of the case as explained in the sec-
tion "2.3 Control panel" on page 6, of this manual.
2 Disconnect the connector "K" (Figure 11.12), see also con-
nector "E" (Figure 11.2).
- 32 -
GAS VALVE
C.H. / D.H.W.
function
Figure 11 .12
3 Turn off the gas supply and disconnect the gas isolation cock
4 Unscrew the connector "M" (Figure 11.12) and remove the
5 Unscrew the screws "L" and remove the valve (Figure 11.12).
6 Reassemble the valve carrying out the removal operations in
Before fitting a new valve, it is advisable to preset it as fol-
lows .
7 Remove the brass plug and turn the plastic screw inside it
8 Turn it counter-clockwise 2 and 3/4 turns.
9 Adjust the gas valve using the flue analyser as described in
After any service operation on the components of the gas
circuit check all the connections for gas leaks .
J
M
K
L
connector from the inlet port of the gas valve.
pipe "J".
reverse order.
Warning: Be careful not to damage the OR gasket of
the gas pipe when inserting the pipe in the air box
(air/gas mixer) .
fully clockwise until it stops. Do not overtight.
section "11.3 Adjustment" on page 30.
Warning: After cleaning or replacement as detailed
above, it is deemed necessary to undertake a com-
bustion analysis as detailed in section "11 .3 Adjust-
ment" on page 30 .