Testing; Replacing The Detector Head; Specifications - Bosch D300A-HV Installation Manual

High-voltage conventional duct detector
Table of Contents

Advertisement

8
en | Specifications
Figure 4.3 Remote Access Memory
1 -
2 -
4.1

Testing

The D300A-HV photoelectric detector has a built-in sensitivity window verification feature. If
the detector is within its calibrated sensitivity range, the detector LEDs flash green in standby
or normal operation. If the detector drifts outside its sensitivity range, the LEDs flash red to
indicate an out of sensitivity condition. Bosch D1000 Calibrated Smoke Detector Tester may
also be used to check sensitivity.
4.2

Replacing the Detector Head

If the detector head supplied with the D300A-HV must be replaced, only replace the existing
head with a D282A-DH Replacement Photoelectric Smoke Detector Head.
1.
2.
3.
4.
5

Specifications

Standby Current
Alarm Current
Alarm Relay Contact Rating
Trouble Relay Contact Rating
Sensitivity Range (Factory Set)
Differential Pressure
Air Velocity
Ambient Temperature
F.01U.035.635 | 5.0 | 2011.09
Black (-)
18
3
Red (+)
19
20
16
1.2 kΩ, 1 W current-limiting resistor
Red "ALARM LED" (15 mA at 24 VDC)
Remove the four screws holding the detector's cover.
Remove the existing detector head by twisting it counterclockwise.
Insert the D282A-DH and turn it clockwise.
Replace the detector's cover and tighten the screws.
1
17
2
16
1
Black (-)
Red (+)
3 -
Key or push button "Test/Reset" switch
(4 A at 24 VDC)
4 -
Green "Pilot" LED (15 mA at 24 VDC)
20 mA at 24 VAC
13 mA at 24 VDC
8 mA at 230 VAC
95 mA at 24 VAC
60 mA at 24 VDC
15 mA at 230 VAC
10 A maximum at 250 VAC resistive
10 A maximum at 250 VAC resistive
1.5%/ft to ~2.75%/ft (4.8%/m to ~ 8.7%/m)
0.01 in. (0.25 mm) - 1 in. (3 cm) of water
300 ft/min to 4000 ft/min (91 m/min to 1219 m/
min)
+32°F to +120°F (0°C to +49°C )
Installation Guide
High-Voltage Conventional Duct Detector
4
Bosch Security Systems, Inc.
3