TEC220x-2 Series Non-Programmable L
Network Configurable
Application Requirements
The TEC220x-2 Series Non-Programmable
L
W
® Network Configurable Staged
ON
ORKS
Thermostats are specifically designed for single-stage
and multi-stage control of heating/cooling equipment,
such as rooftop and heat pump units.
Accurate temperature control is achieved with a time
proportional control algorithm, which virtually
eliminates the temperature offset associated with
traditional, differential-based thermostats. For more
advanced applications, an economizer control logic
has been integrated onto the thermostat for use with
proportional damper economizer actuators.
All programmable models contain a Single-Pole
Single-Throw (SPST) auxiliary switch, which can be
used to control lighting or disable the economizer
function.

Mechanical Installation

Location
Install away from any heat source.
Do not install the thermostat:
on an outside wall
near an air discharge grill
in a location affected by direct sun radiation
in an area that restrains vertical air circulation to
the thermostat
Figure 1: Bottom of Thermostat
© 2005 Johnson Controls, Inc.
Code No. LIT-1201911
Installation Instructions
ON
Staged
Thermostats
Installation
To install the thermostat:
Note: Wall surface must be flat and clean.
1.
Remove security screw on the bottom of
thermostat cover.
2.
Open up by pulling on the bottom side of
thermostat (Figure 1).
3.
Swing the thermostat circuit board to the left by
pressing the pull tabs (Figure 2).
4.
Pull cables 6" out of the wall.
5.
Insert cable in the central hole of the base.
6.
Align the base and mark the location of the two
mounting holes on the wall. Install proper side of
base up.
Figure 2: Pull Tabs
7. Install anchors in the wall.
8. Insert screws in mounting holes on each side of
the base (Figure 2).
9. Gently swing the circuit board back on the base
and push until the tabs lock.
10. Pull out the screw terminal blocks using the pull
tabs on each connector (Figure 3).
Issue Date
November 23, 2005
W
®
ORKS
www.johnsoncontrols.com
Software Release 1.0
1

Advertisement

loading

Summary of Contents for Johnson Controls TEC2201-2

  • Page 1: Mechanical Installation

    9. Gently swing the circuit board back on the base and push until the tabs lock. 10. Pull out the screw terminal blocks using the pull tabs on each connector (Figure 3). Figure 1: Bottom of Thermostat © 2005 Johnson Controls, Inc. Code No. LIT-1201911 www.johnsoncontrols.com Software Release 1.0...
  • Page 2: Electrical Installation

    11. Strip each wire 1/4 inch. Wiring If the same power source is used for the heating 12. Insert each wire according to wiring diagram. stages, install jumper across RC and RH. Maximum 13. Gently push excess wiring back into the hole. current is 2.0 amperes.
  • Page 3: Wiring Analog Outputs

    0 mA @ 140°F (60°C) Table 3: Thermostat Models Application 1 Heat/1 Cool 2 Heat/2 Cool 2 Heat/2 Cool Heat Pump and Economizer Model (Non-Programming TEC2201-2 TEC2203-2 TEC2204-2 TEC2202-2 without Scheduling) TEC220x-2 Series Non-Programmable L Network Configurable Staged Thermostats Installation ORKS Instructions...
  • Page 4: Non-Programmable Thermostat Wiring

    Non-Programmable Thermostat Wiring TEC2201-2 Single-Stage Thermostat The TEC2201-2 features one fan, one heating stage, and one cooling stage. Figure 4 shows a wiring example. Thermostat Terminals – TEC2201-2 Scom Digital Input #1 Jumper J1 Digital Input #2 Scom Heat Remote...
  • Page 5 TEC2204-2 Economizer Thermostat The TEC2204-2 features one fan, two heating stages, two cooling stages, and an economizer. Figure 6 shows a wiring example. Thermostat Terminals – TEC2204-2 DI1 DI2 Scom Digital Input #1 Jumper J1 Digital Input #2 Scom Cool Heat 0-10 Vdc Remote...
  • Page 6: Technical Specifications

    The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.

This manual is also suitable for:

Tec2204-2Tec2203-2Tec2202-2