Download Print this page
Danfoss TGE 10 Installation Manual

Danfoss TGE 10 Installation Manual

Thermostatic expansion valves

Advertisement

Quick Links

Installation guide
Thermostatic expansion valves
Type TGE 10, TGE 20 and TGE 40
Refrigerants:
R410A, R32, R452B, R454B, R22, R134a, R1234ze, R407F, R407A, R404A,
R507, R407C and R290
For complete list of approved refrigerants, go to www.danfoss.com
Note: Only solder version, connection sizes 28 mm / 1
This product is approved for R290 by ignition source assessment in accordance to standard EN13463-1.
TGE 10 Balanced port design
MAH charge: 150 °C / 302 °F
N charge: 100 °C / 210 °F
K charge: 150 °C / 302 °F
Max. 700 °C
/ 1300 °F
© Danfoss | DCS (az) | 2018.02
Max. working pressure:
PS/MWP = 46 bar / 667 psig
1
/
inch and below are approved for flammable refrigerants.
8
Max. 700 °C
/ 1300 °F
Max. 110 °C
/ 230 °F
OK
TGE 20 / TGE 40 Double balanced port design
1
/
-
5
/
inch
2
8
12 - 16 mm
/
-
/
inch
3
7
4
8
18 - 22 mm
2
1 - 1
3
/
inch
8
25 - 35 mm
Max. test pressure:
P
= 51 bar / 740 psig
test
OK
Min. 5% Ag
1
3
Torx T25
Max. torque 4 Nm / 3 ft-lbf
DKRCC.PI.AXV.A7.02 | 1