Pentair FreezGard CCH-1C Installation Instructions

Self-regulating crankcase heater

Advertisement

Quick Links

SELF-REGULATING CRANKCASE HEATER INSTALLATION INSTRUCTIONS
APPROVALS
–G
WARNING:
FIRE AND SHOCK HAZARD: This heater is an electrical device
that must be installed correctly to ensure proper operation and to
prevent shock or fire. Read these important warnings and carefully
follow all the installation instructions.
THERMAL BUILDING SOLUTIONS
FreezGard
• To minimize the danger of fire from sustained electrical arcing
if the crankcase heater is damaged or improperly installed,
ground-fault equipment protection must be used on each
branch circuit supplying power to the crankcase heater. Arcing
may not be stopped by conventional circuit breakers.
• Do not damage the heating cable, strap, or electrical lead wires.
Remove any damaged cables from service immediately.
EN-RaychemFreezGardCrankCase-IM-H55593      06/16
DESCRIPTION
FreezGard crankcase heaters are intended for professional
installation on refrigeration compressors up to 5 horsepower and
40 inches or less in circumference.
MODELS AVAILABLE
CCH-1C
For use with 120 Vac power supply
CCH-2C
For use with 208 – 277 Vac power supply
ADDITIONAL MATERIALS REQUIRED
UL Listed or CSA Certified junction box and appropriate
connection accessories.
GENERAL REQUIREMENTS
• FreezGard heaters are intended for use on refrigeration
compressors. For any other applications, call Pentair Thermal
Management for assistance.
• FreezGard heaters may be used only on metal hermetic
compressors up to 40 inches in circumference.
• Never use on any compressor that may exceed 150°F.
• Do not use an extension cord to power the crankcase heater.
• Electrical connections must be in accordance with the National
Electrical Code and must be protected from rain and other water.
• Prior to installing the heater, clean the compressor surface and
inspect for and remove any sharp surfaces that may damage the
heater.
• FreezGard cables must be installed by professional HVAC or
refrigeration technicians or equivalent.
• Ground-fault circuit breakers such as the Square D QO-EPD,
QOB-EPD, or equivalent, with a 30-mA trip level, should be
used. For technical assistance or availability, call Pentair
Thermal Management at (800) 545-6258.
• Leave these Installation Instructions with the user for future
reference.
• If you have any questions about how to use or install this
crankcase heater, please call Pentair Thermal Management at
(800) 545-6258.
1 / 2

Advertisement

loading

Summary of Contents for Pentair FreezGard CCH-1C

  • Page 1 UL Listed or CSA Certified junction box and appropriate connection accessories. GENERAL REQUIREMENTS • FreezGard heaters are intended for use on refrigeration compressors. For any other applications, call Pentair Thermal Management for assistance. • FreezGard heaters may be used only on metal hermetic APPROVALS compressors up to 40 inches in circumference.
  • Page 2 Fax: +1.650.474.7711 thermal.info@pentair.com Pentair and FreezGard are owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the right to change specifications without prior notice. © 1997-2016 Pentair. THERMAL BUILDING SOLUTIONS EN-RaychemFreezGardCrankCase-IM-H55593      06/16...

This manual is also suitable for:

Freezgard cch-2c