Specification - ABB SM500F Commissioning Instructions

Field-mountable paperless recorder
Hide thumbs Also See for SM500F:
Table of Contents

Advertisement

Restriction of Hazardous Substances (RoHS)
The European Union RoHS Directive and subsequent
regulations introduced in member states and other
countries limits the use of six hazardous substances
used in the manufacturing of electrical and electronic
equipment. Currently, monitoring and control
instruments do not fall within the scope of the RoHS
Directive, however ABB has taken the decision to
adopt the recommendations in the Directive as the
target for all future product design and component
purchasing.

Specification

EMC
Emissions & immunity
Meets requirements of IEC61326 for an Industrial Environment
Electrical
Supply ranges
100 V to 240 V AC ± 10% (90 V min to 264 V max) or
105 V DC min. to 115 V DC max.
10 V to 36 V DC (optional)
Power consumption
10 W max.15 VA max.
Power interruption protection
No effect for interrupts of up to 20 ms
Safety
General safety
EN61010-1
Overvoltage Class III on mains, Class II on inputs and outputs
Pollution category 2
CSA 61010-1
UL 61010-1
Isolation
500 V DC to earth (ground)
CI/SM500F–EN Rev. A
Environmental
Operating temperature range
–10 to 50 °C (14 to 122 °F)
Operating humidity range
5 to 95 %RH (non-condensing)
Storage temperature range
–20 to 70 °C (–4 to 174 °F)
Enclosure sealing
IP66 and NEMA4X (the enclosure meets the requirements of
the NEMA 4X hosedown test)
Vibration
Conforms to EN60068–2–6
3