ABB SM500F Commissioning Instructions page 10

Field-mountable paperless recorder
Hide thumbs Also See for SM500F:
Table of Contents

Advertisement

1 2
3
4
1 2
Voltage
1 2
3
4
1
Each lead must be of equal
resistance and less than 10 
3-lead RTD
4-lead RTD
*In the powered-down condition the current input is open circuit.
In order to maintain a current loop when the recorder is powered
down, fit a zener diode (BZX79 – B/C2V4) to the input as shown.
Fig. 8 Single analog / digital input connections
Input 1 Input 2
Input 1 Input 2
1 2
3
4
Voltage
*In the powered-down condition the current
input is open circuit. In order to maintain a
current loop when the recorder is powered
down, fit a zener diode (BZX79 – B/C2V4) to
the input as shown.
Fig. 9 Dual analog / digital input connections
IMPORTANT (NOTE) Tighten all analog / digital input
terminal screws to a torque of 0.5 Nm (4.5 lbf.in).
10
3
4
1 2
Current
Thermocouple
2
3
4
1 2
Logic state inactive
Logic state active
Digital input
(volt-free or 24 V)
Input 1 Input 2
1 2
3
4
1 2
Current
Thermocouple
Input 1 Input 2
1 2
Logic state inactive
Logic state active
Digital input
(volt-free or 24 V)
Power supply connections
3
4
Fuse
305 mA, type T
Line
Neutral
Warning. Use fuse rating 315 mA (max.) type T
3
4
Fuse
1.5 A, type T
Warning. Use fuse rating 1.5 A (max.) type T
Fig. 10 Power supply connections
IMPORTANT (NOTE) Tighten power supply terminal
screws to a torque of 0.8 Nm (7 lbf.in).
3
4
Transmitter power supply module
One transmitter power supply module can be fitted in position D
to provide a nominal 24 V supply capable of driving two, 2-wire
transmitters.
3
4
Fig. 11 Power supply connections
100 V min. to 240 V max,
50 / 60 Hz
A – AC supply
10 V min. to 36 V max, DC
B – DC supply
2-wire transmitter power supply
(24V DC, 22mA max.)
Tx
Analog input
1 2
3
4
CI/SM500F–EN Rev. A

Hide quick links:

Advertisement

Table of Contents
loading