Power Connection Guidelines

Step 2
Slide the open end of your 2-hole ground lug over the exposed area of the ground wire.
Step 3
Using a crimping tool (as specified by the ground lug manufacturer), crimp the ground lug to the ground wire as shown
in the figure below.
Figure 22:
Step 4
Use a Phillips head screwdriver to attach the 2-hole ground lug and wire assembly to the router with the 2 pan-head
Phillips head screws.
Step 5
Connect the other end of the ground wire to a suitable grounding point at your site.
Power Connection Guidelines
This section provides guidelines for connecting the router power supplies to the site power source.
Never defeat the ground conductor or operate the equipment in the absence of a suitably installed ground
Warning
conductor. Contact the appropriate electrical inspection authority or an electrician if you are uncertain
that suitable grounding is available. Statement 213
The plug-socket combination must be accessible at all times because it serves as the main disconnecting
Warning
device. Statement 1019
Cisco ASR 920 Series Aggregation Services Router Hardware Installation Guide
28
Prevent Power Loss
Activate a DC Power Supply
Activate an AC Power Supply
Installing the Cisco ASR 920 Series Router